8.5 Self-Diagnostics

8.5.1 Checking for Problems

(1) Identifying Problems with BT200

The following four areas can be checked.
(a) Whether connections are good.
(b) Whether BT200 was properly operated.
(c) Whether settings were properly entered.
(d) History of the errors.
See examples below.
• Example 1: Connection errors
––WELCOME––
BRAIN TERMINAL
ID:
BT200
check connection
push ENTER key
UTIL
FEED
communication error
ESC
• Example 2: Setting entry errors
PARAM
01:MODEL
EJA110A-DM
02:TAG NO.
YOKOGAWA
03:SELF CHECK
ERROR
OK
PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
600 kPa
C22:HIGH RANGE
600 kPa
DATA
DIAG
PRNT
ESC
DIAG
C60:SELF CHECK
ERROR
<
ERROR
>
<
ILLEGAL LRV >
FEED
PRNT
ESC
Press the
key.
When the panel shown on the left
appears, press the
Since communications will be
unsuccessful if there is a problem
in the connection to the BT200, the
display at the left will appear.
Recheck the connection.
Press the
(OK) key.
The initial data panel shows the
result of current transmitter
diagnostics.
Press the
(DIAG) key in the
parameter panel to go to the
diagnostics panel
(C60: SELF CHECK).
An error message is displayed
when an error occurs in the
diagnostics panel.
• Example 3: Checking the history of the errors
MENU
J:ADJUST
K:TEST
M:MEMO
P:RECORD
HOME
SET
PARAM
P10:ERROR REC 1
ERROR
P11:ERROR REC 2
ERROR
P12:ERROR REC 3
GOOD
DATA
DIAG
P10: "ERROR REC 1" displays the last error.
P11: "ERROR REC 2" displays the error one time before
the last error occurred.
P12: "ERROR REC 3" displays the error two times before
the last error occurred.
P13: "ERROR REC 4" displays the error three times before
key.
the last error occurred.
The history of up to four errors can be stored. When the 5th
error has occurred, it is stored in "P10". The error stored in
"P13" will be deleted, and then, the error in "P12" will be
copied to "P13". In this sequence, the history of the most
previously occurred error will be removed from memory.
"GOOD" will be displayed if there was no previous error.
SET
P10:ERROR REC 1
ERROR
<
ERROR
<
ILLEGAL LRV >
<
ILLEGAL HRV >
<(a) SETUP PANEL>
For the details of the messages listed below, see Table
8.5.1 Error Message Summary.
CAP MODULE FAULT
AMP MODULE FAULT
OUT OF RANGE
OUT OF SP RANGE
Note 1: Press the
(panel 1) to clear all error message (P10 to P13)
information.
Note 2: After two hours from when an error occurs, the error
message of that error will be recorded. Therefore,
if you switch off the transmitter within two hours from
F0842.EPS
when the error occurs, there is no history of that
error stored in the transmitter, and this function is
meaningless.
8-17
8. BRAIN TERMINAL BT200 OPERATION
Connect the BT200 to the
transmitter, and call item "P."
ADJ
ESC
PRNT
ESC
Select P10: ERROR REC1 and
press the
>
the error message.
ESC
OVER TEMP (CAP)
OVER TEMP (AMP)
OVER OUTPUT
OVER DISPLAY
key twice in the setting panel
key to display
ILLEGAL LRV
ILLEGAL HRV
ILLEGAL SPAN
ZERO ADJ OVER
F0843.EPS