Csa Certification - YOKOGAWA DPharp EJX110A User Manual

Differential pressure and pressure transmitters
Hide thumbs Also See for DPharp EJX110A:
Table of Contents

Advertisement

b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJX Series pressure transmitters
with optional code /FF1 are applicable for
use in hazardous locations.
• Applicable Standard: FM3600, FM3615,
FM3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1,
Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Enclosure rating: NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40* to 60°C
* –15°C when /HE is specified.
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NFPA70 and Local Electrical
Codes.
• When installed in Division 1, "FACTORY
SEALED, CONDUIT SEAL NOT
REQUIRED."
Note 3. Operation
• Keep the "WARNING" nameplate attached to
the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. FACTORY SEALED,
CONDUIT SEAL NOT REQUIRED.
INSTALL IN ACCORDANCE WITH THE
USERS MANUAL IM 01C25.
• Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void
Factory Mutual Explosionproof Approval.
c.
FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJX Series pressure transmitters with
optional code /FU1 or /V1U can be selected the
type of protection (FM Intrinsically Safe or FM
Explosionproof) for use in hazardous locations.
<2. Handling Cautions>
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
2.9.2 CSA Certification
a.
CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe and
nonincendive type. (Following contents refer to
"DOC No. ICS013-A13")
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with
optional code /CS1 are applicable for use
in hazardous locations
Certificate: 1606623
[For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2
No.0.4, C22.2 No.25, C22.2 No.94, C22.2
No.157, C22.2 No.213, C22.2 No.1010.1
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1,
Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division 2, Groups
A, B, C & D, Class II, Division 2, Groups E, F
& G, Class III, Division 1
• Enclosure: Type 4X
• Temp. Code: T4
• Amb. Temp.:–50* to 60°C
* –15°C when /HE is specified.
• Process Temperature: 120°C max.
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-0,
CAN/CSA E60079-11, CAN/CSA E60079-15,
IEC 60529:2001-02
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50* to 60°C
* –15°C when /HE is specified.
• Max. Process Temp.: 120°C
• Enclosure: IP66 and IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 200 mA
Maximum Input Power (Pmax/Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
2-5