Hitachi WJ200 Series Instruction Manual page 178

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
PID FBV output
C053
low limit
Over-torque/under-torque
C054
selection
Over/under-torque level
C055
(Forward powering mode)
Over/under-torque level
C056
(Reverse regen. mode)
Over/under-torque level
C057
(Reverse powering mode)
Over/under-torque level
C058
(Forward regen. mode)
Signal output mode of
C059
Over/under-torque
Electronic thermal
C061
warning level
Zero speed detection level
C063
Heat sink overheat
C064
warning
Overload warning level 2
C111
"C" Function
Description
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
Two option codes:
00...Over-torque
01...Under-torque
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Set range is 0 to 200%
Two option codes:
00...During accel.,
decel. and constant
speed
01...During constant speed only
Set range is 0 to 100%
Setting 0 means disabled.
Set range is 0.0 to 100.0Hz
Set range is 0 to 110 °C
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Run
Defaults
Mode
Lnitial data
Units
Edit
0.0
00
100.
100.
100.
100.
01
90
0.00
100.
Rated current
x 1.15
3−97
%
%
%
%
%
%
Hz
°C
A