Hitachi WJ200 Series Instruction Manual page 126

Wj200 series single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Automatic restart (retry) related parameters.
Func.
Name
Code
Restart mode on power
B001
failure / under-voltage trip
Allowable under-voltage
B002
power failure time
Retry wait time before motor
B003
restart
Instantaneous power failure
B004
/ under-voltage trip alarm
enable
Number of restarts on power
B005
failure / under-voltage trip
events
Restart frequency threshold
b007
"b" Function
Description
Select inverter restart method,
Five option codes:
00...Alarm output after trip, no
automatic restart
01...Restart at 0Hz
02...Resume
frequency matching
03...Resume previous freq.
after freq. matching, then
decelerate to stop and
display trip info
04
...Resume operation after
active freq. matching
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
Time delay after under-voltage
condition goes away, before the
inverter runs motor again.
Range is 0.3 to 100 seconds.
Three option codes:
00...Disable
01...Enable
02...Disable during stop and
decelerates to a stop
Two option codes:
00...Restart 16 times
01...Always restart
Restart the motor from 0Hz if
the frequency becomes less
than this set value during the
motor is coasting, range is 0 to
400Hz
Run
Mode
Edit
operation
after
3−45
Defaults
Lnitial data
Units
00
1.0
sec.
1.0
sec.
00
00
0.00
Hz