2. Installation
(6) Configure the baud rate, MAC ID (master address), and so on for the DeviceNet
The load on a bus can be controlled by the baud rate and interscan delay settings.
NOTE
When the load exceeds 60%, the DeviceNet network communication will be unstable, for
example: more communication errors. Set the configuration to minimize the load.
For the procedure for verifying the load on the bus using the applicomIO Console
application, refer to the 4. Troubleshooting in this manual.
(7) Click the Network Detection tab on the center left of the console window.
(8) Click the Read Network Configuration button to display the Network Detection
32
network.
dialog and read in the devices on the Fieldbus.