Shield Wire
Communication Cable Signal
Terminating Resistor
To reduce reflections of communication signal, terminating resistors should be attached on
both ends of the trunk line. For DeviceNet, nodes have no terminating resistor on the ends.
Attach 121 Ω +/-1%, 1/4W terminating resistors between the signal wires (CAN-H and CAN-
L) of the trunk line cable. Some T-branch taps and connectors can accept terminal resistors.
Molded terminating resistors with connectors are also available to attach to environment-
resistant T-branch taps and connectors.
Node Connection
Nodes can be connected to a DeviceNet network by the following topologies: tree, multi-drop,
T-branch, daisy chain. For tree topology, there is no limitation of daisy chain layer but drop
line length is limited. For details of drop line length, refer to the following section "Drop
Line Length".
Terminating
Resistor
Communications Power Supply
DeviceNet supplies 24V DC communications power to each node via 5-wire cables. You can
install the communications power supply at any location on the DeviceNet network. We
recommend providing a dedicated communications power supply on the network separately
even though it is possible to share power among the communications power supply, node
internal circuit power supply, and I/O power supply.
Shield Ground of Signal Wire
Ground the DeviceNet network at one point with 100 Ω or less.
As a noise countermeasure, you can leave the network ungrounded. For details, refer to the 4.
Troubleshooting.
Fieldbus I/O Rev.6
Thick Cable
11.2 to 12.1 mm outside diameter
Braid Shield
Signal Wire
(Blue/White)
Power Wire
(Red/Black)
Wire Type
Color
Blue
Signal wire
White
Red
Power wire
Black
Shield wire
-
Trunk Line
Tree
Multi-drop
6.9 mm outside diameter
Shield Wire
Details of Signal
Signal Low
Signal High
Communications Power Positive
Communications Power Negative
Shield
Branch Tap
T-branch
2. Installation
Thin Cable
Braid Shield
Signal Wire
(Blue/White)
Power Wire
(Red/Black)
Wire Identity
CAN L
CAN H
V+
V
S
Terminating
Resistor
Daisy Chain
13