2. Remove and retain the two screws holding the internal battery
connector. Disconnect the internal battery connector. See
Figure 26.
Internal
Battery
Connector
3. Remove and retain the two screws holding the battery cover plate.
Grasp an edge of the battery cover plate and pull it forward gently.
Remove and retain the battery cover plate.
4. Carefully pull the handle on the battery tray and slide the battery
package slowly out onto a flat, stable surface; use two hands to
support the battery package. See "Recycling the Used Battery or
UPS" on page 73 for proper disposal.
NOTE Verify that the replacement batteries have the same rating as the batteries being
replaced.
5. Slide the new battery package into the cabinet. Push the battery
package in firmly.
Eaton
®
9130 UPS (700–3000 VA) User's Guide
Battery Tray Handle
Figure 26. Replacing the UPS Internal Batteries