For more information, contact your local recycling/reuse or hazardous waste center. This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Information, advice, help. Page 2 9130 UPS-EN...
6.5 Testing New Batteries ...29 6.6 Recycling the Used Battery or UPS ...30 7. Specifications 7.1 Model Specifications ...31 8. Troubleshooting 8.1 Typical Alarms and Conditions ...34 8.2 Silencing the Alarm ...36 8.3 Service and Support ...36 9130 UPS-EN Contents Page 3...
— causing hours of lost productivity and expensive repairs. With the Eaton 9130, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the Eaton 9130’s unique benefits...
Discard or recycle the packaging in a responsible manner, or store it for future use. Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable gas, and corrosion. 9130 UPS-EN 2. Installation Page 5...
Toll Free: 1.800.356.5794 or 919.872.3020 Service and support: United States: 1-800-843-9433 or 1-919-870-3028 Canada: 1-800-461-9166 ext 260 All other countries: Call your local service representative E-mail: InsideSalesEngineerUPS@eaton.com EATON 9130 UPS 5000 - 6000 VA User's guide 9130 UPS-EN 9130 UPS-EN...
22 to install the RPO switch before powering on the UPS. 6. If you are installing EBM(s), continue to the following section, "Connecting the EBM(s)". Otherwise, continue to "Installation requirements" on page 8. 9130 UPS-EN 2. Installation Page 7...
Input and Bypass inputs are identical, and upstream protection is provided by only one switch with RCD (residual current device) for Input and Bypass inputs. 9130 UPS-EN Minimum of section Terminal-block capacity required 6 mm²...
Page 10
Frequency converter (without Bypass input) (Figure 15) Configuration used when the frequency of the application differs from the Mains, example: marine requirements. Main low voltage switchboard (MLVS) Page 10 Bypass Input Output Bypass Output Input Bypass Output Input Input Output Load Load Load Load 9130 UPS-EN...
Always connect the earthing wire first. BYPASS INPUT JP L Figure 17. 9130 UPS-EN 3. Power cables connection & Startup 1 - Make sure the metal jumper is connected OUTPUT (see figure 17). 2 - Insert the Input source cable through the cable gland.
5 - Connect the 3 cables to the output terminal block. 6 - Put back and secure the terminal block cover with the 2 screws. 7 - Tightened the cable glands. Do not connect anything to the Bypass terminal block. 9130 UPS-EN...
The internal batteries charge to 90 % capacity in less than 3 hours. However, Eaton recommends that the batteries charge for 48 hours after installation or long-term storage. If optional EBMs are installed, see the recharge times listed in table 24 on page 33. 9130 UPS-EN 3. Power cables connection & Startup Page 13...
4. Operation This chapter contains information on how to use the Eaton 9130, including front panel operation, operating modes, UPS startup and shutdown, transferring the UPS between modes, retrieving the Event Log, setting the power strategy, and configuring bypass settings, load segments, and battery settings.
Frequency Converter Overload Alarm Level Transfer to Bypass When Overload* 9130 UPS-EN Display Information or Menu Function Main status (mode and load) / Notice or Alarm status (if any) / Battery status (state and charge level) Displays up to 127 events and alarms.
Page 16
Normal No Delay Disabled Enabled Disabled No Delay 120 s Enabled -15 % of nominal +10 % of nominal When in Spec ±3 Hz Enabled ABM Cycling Enabled Not Checked 3 min Enabled Enabled Disabled Enabled Enabled Open 9130 UPS-EN...
Operating Modes The Eaton 9130 front panel indicates the UPS status through the UPS indicators (see figure 20 on page 14). Normal Mode During Normal mode, the The UPS monitors and charges the batteries as needed and provides filtered power protection to your equipment.
From Bypass to Normal Mode. Press any button to activate the menu options, then select CONTROL and GO TO NORMAL. Page 18 indicator illuminates solid, indicating that the UPS is operating normally and any indicator turns off. indicator illuminates solid. The 9130 UPS-EN...
("Sync Disabled"), the UPS will synchronize only when operating on Bypass. Unsynchronized Transfers. The default allows an unsynchronized transfer to Bypass. You can configure the setting to not allow such transfers. This setting can be overruled by the "Qualify Bypass" setting. 9130 UPS-EN 4. Operation Page 19...
You can set the load segment for the amount of time to delay the restart once utility returns, using the "Automatic Start Delay" setting. You can also configure UPS restart to depend on the battery charge level, using the "Battery Charge % to Restart" setting. Page 20 Number of Battery Strings 1 (default) 9130 UPS-EN...
3. Continue to "Operation" on page 14 to start up the UPS. Communication Options The Eaton 9130 has serial communication capabilities through the USB and RS-232 communication ports or through a connectivity card in the available communication bay. The UPS supports two serial communication devices according to the following table 7:...
Page 22
Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Eaton 9130 has one available communication bay for the following connectivity cards: Connect UPS-MS Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
Page 23
The relay output contacts must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The relay output contacts have a maximum rating of 30 Vac/1A and 60 Vdc/2A nominal values. 9130 UPS-EN Terminal Wire Size Rating 4–0.32 mm² (12–22 AWG)
Page 24
The batteries continue charging. Inactive input does not abort the shutdown countdown but will cause the UPS to start up automatically if the input voltage exists. If active, synchronization is disabled and the UPS transfers to bypass. If active, the UPS generates the "Building Alarm 1" alarm. 9130 UPS-EN...
When installing software, select serial port installation. For the UPS manufacturer and model, select Eaton and Eaton 9130. If the Eaton brand options are not available in your version of the software, select Generic UPSs for the manufacturer and Generic XCP for the model.
Batteries can be replaced easily without turning the UPS off or disconnecting the load. If you prefer to remove input power to change the batteries, see "UPS Shutdown" on page 18. Consider all warnings, cautions, and notes before replacing batteries. Page 26 9130 UPS-EN...
Page 27
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect Figure 27. Removing the UPS front cover. 2. Disconnect the internal battery connector (see figure 28). 9130 UPS-EN 6. UPS Maintenance Page 27...
Page 28
See "Recycling the Used Battery or UPS" on page 30 for proper disposal. Verify that the replacement batteries have the same rating as the batteries being replaced. Repeat step 3-4-5 if several battery tray need to be removed. Page 28 9130 UPS-EN...
During the battery test, the UPS transfers to Battery mode and discharges the batteries for 25 seconds. The front panel displays "Battery test running" and the percentage of the test completed. 9130 UPS-EN 6. UPS Maintenance Page 29...
For more information, contact your local recycling/ reuse or hazardous waste center. Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Page 30 9130 UPS-EN...
PW9130N6000T-EBM Table 17. Electrical Input Nominal Frequency Frequency Range Bypass Voltage Range Noise Filtering 9130 UPS-EN (1) available independent communication bay for connectivity cards Connect UPS-MS Web/SNMP Card Relay Interface Card RS-232 (DB-9): 1200–9600 bps USB: 9600 bps (4) programmable signal inputs (signal and signal return) for indicating...
Page 32
High Efficiency mode: 10 ms maximum (due to loss of utility) 3 to 1 Output Connections Output Cables Hardwired None Voltages at 100 % Load 180–276 Vac 180–276 Vac Battery Mode Nominal output voltage ±3 % > 92 % ±0.1 Hz of auto-selected nominal frequency 9130 UPS-EN...
Page 33
Monitoring Recharge Time (to 90 Battery Port EBM battery cable length 9130 UPS-EN EN 61000-2-2 EN 61000-4-2, Level 3 EN 61000-4-3, Level 3 EN 61000-4-4, Level 3 (also on signal ports) EN 6100-4-5, Level 3 Criteria A (IEEE C62.41 6 KV)
8. Troubleshooting The Eaton 9130 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
The UPS does not transfer to Bypass mode. USB communication does not work. 9130 UPS-EN Power requirements exceed the Remove some of the equipment from UPS capacity (greater than 100 the UPS. % of nominal; see page 31 for The UPS continues to operate, but specific output overload ranges).
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you. Page 36 9130 UPS-EN...