OPERATION
Table 3. User Settings (continued)
Description
Site Wiring Fault Alarm
Bypass Voltage Low Limit*
Bypass Voltage High Limit*
Qualify Bypass*
Synchronization Window*
Unsynchronized Transfers*
Number of Battery Strings
Battery Charge Mode
Temperature Compensated Charging
Battery Charge % to Restart
Battery Low Alarm
Automatic Battery Support Tests
Ambient Temperature Warning
* See "Configuring Bypass Settings" on page 48.
42
Eaton
®
9130 UPS (700–3000 VA) User's Guide
Available Settings
[Enabled] [Disabled]
An active site wiring fault alarm prevents
startup or, if operating, forces operation to
Battery mode and disables bypass.
[-4%] [-5%] ... [-20%] of nominal
[+4%] [+5%] ... [+20%] of nominal
[Never] [When in Spec] [Always on UPS Fault]
[Always]
[Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±2.0 Hz]
[±3.0 Hz]
[Enabled] [Disabled]
[0] [1] [2] ... [10]
See "Configuring the UPS for EBMs" on
page 51.
[ABM Cycling] [Constant]
[Enabled] [Disabled]
If Disabled, the default charger voltages for
25°C (77°F) are assumed.
[Not Checked] [10] [20] ... [100]
If a percentage is selected, automatic restart
(if enabled) occurs when the battery's charge
reaches the selected level.
[Immediate] [2 min] [3 min] [5 min]
The "Battery Low" alarm triggers when the
set amount of backup time (approximately)
remains in the batteries. If set to Immediate,
the alarm activates at the same time as the
"UPS on Battery" notice.
[Enabled] [Disabled]
See "Running Automatic Battery Tests" on
page 52.
[Enabled] [Disabled]
S
164201718 Rev 2 www.powerware.com
Default Setting
Enabled
-15% of nominal
+10% of nominal
When in Spec
±2.0 Hz
Enabled
1
ABM Cycling
Enabled
Not Checked
3 min
Enabled
Enabled