Page 1
Powerware Series ® Eaton 9135 Two-in-One UPS 5000/6000 VA User's Guide...
Page 2
Phillips Screw Company. All other trademarks are property of their respective companies. ECopyright 2009–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Page 3
Class A EMC Statements FCC Part 15 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to NOTE part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
— causing hours of lost productivity and expensive repairs. With the Eaton 9135, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Eaton 9135 UPS.
Page 8
INTRODUCTION Providing outstanding performance and reliability, the Eaton 9135's unique benefits include: Online UPS design with pure sine wave output. The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery. Two-in-one form factor for using the UPS in a rack-mount configuration or as a standalone cabinet.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 10
Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må ikke overstige 40°C. UPS'en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%). 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
0 V. Als de ingangsbedrading loopt van fase naar fase dan bedraagt de spanning op de uitgangscontactdozen 115V (gemeten tussen fase en aarde of tussen fase en neutraal, afhankelijk van de UPS-bedrading). 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 12
Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. Vervang de accu's door accu's met hetzelfde nummer en van hetzelfde type als de oorspronkelijke accu's in de UPS. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 13
Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. Vaihda UPS-virtalähteeseen vain samanlaiset akut ja sama määrä akkuja kuin siinä oli alun perin. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 14
La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d'eau ou dans une atmosphère excessivement humide (95 % maximum). 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Ausgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Außenleitern beträgt die Spannung an den Ausgangssteckverbindern 110–120 Volt (gemessen von Leitung zu Masse oder Leitung zu Masseleiter, abhängig von der UPS (USV)-Verkabelung. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All'interno del gruppo statico di continuità NON vi sono PARTI RIPARABILI DALL'UTENTE. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 17
Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. Sostituire le batterie con altre dello stesso numero e tipo di quelle originariamente installate nell'UPS. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i nærheten av vann eller ved meget høy luftfuktighet (95% maks.). 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 19
A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%). 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. Reemplace las baterías con el mismo número y tipo de baterías como se instalaron originalmente en el SAI. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 23
Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Byt ut batterierna mot samma antal och typer av batterier som ursprungligen installerats i UPS-enheten. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Rackmounting kit for 19-inch (48 cm) bays Two sets of pedestals with screws for tower position Optional. Network Management Card EU models only. Four cord-retention brackets EU models only. Four, 10A equipment power cords 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 27
Description EBM user's guide EBM cable EBM communication cable Rackmounting kit for 19-inch (48 cm) bays Pedestal extenders for tower position Joining bracket and screws for tower position 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Slide the battery connector so that you can read Connected (see Figure 3). Reinstall the two screws removed in Step 2. Continue to the following section, “UPS Setup.” Figure 3. Connecting the Internal Battery Connector 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
INSTALLATION UPS Setup The Eaton 9135 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section, “Rackmount Setup;” otherwise, continue to “Tower Setup” on page 30.
DO NOT install the UPS or EBM in a hermetically-closed environment without any exchange of air. The UPS and EBM are heavy (see page 67): 1) Eaton strongly recommends to remove the battery tray from the UPS before lifting. 2) A minimum of two people are required to lift the cabinets into the rack.
Page 31
Place the front panel above the UPS. Remove the two battery retaining brackets (four screws). Slightly pull the battery tray, then lift it to extract it. Figure 5. Removing the Battery Tray 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 32
M4 6 mm flat-head screws. If installing additional cabinets, repeat Steps 3 and 4 for each cabinet. Figure 6. Installing the Mounting Brackets 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 33
Secure the rail to the front of the rack with two M6 12 mm screws. 10. Repeat Steps 8 and 9 for the other rail. Figure 7. Installing the Rails 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 34
13. Secure the front of the cabinet to the rack using two M6 12 mm round-head screws on each side (see Figure 9). Figure 9. Installing the Cabinets 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 35
15. If you removed the UPS battery tray in Step 2, replace the battery tray and secure with the battery retaining brackets. Replace the UPS front cover. 16. Continue to “Installing the UPS” on page 35. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Carefully position the cabinet upright with the UPS indicators at the top and place in the pedestals (see Figure 12). Adjust the pedestals to the size of the UPS and secure the pedestals with the captive screws. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 37
INSTALLATION UPS Indicators 150 mm (6”) 450 mm (17.7”) Figure 12. Tower Position with One Cabinet Continue to the following section, “Installing the UPS.” 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 38
Figure 13. Extending the Pedestals for Two Cabinets 1 2 3 4 1 2 3 4 1 2 3 4 Figure 14. Extending the Pedestals for Three or More Cabinets 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 39
(see Figure 15). Adjust the pedestals to the size of the UPS and secure the pedestals with the captive screws. Figure 15. Tower Position with Two Cabinets 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 40
Joining Bracket Figure 16. Installing the Joining Brackets 10. If installing additional EBMs, repeat Step 6 for each cabinet. 11. Continue to the following section, “Installing the UPS.” 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
RJ-11 port. See Figure 17. Up to four EBMs may be connected to the UPS. EBM Cable Battery Circuit Communication Breaker Cable EBM Battery Connectors Figure 17. UPS Installation with Three EBMs 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 42
If you are installing a remote power-off (RPO) switch, see the following section, “RPO Installation,” to install the switch before powering on the UPS. Continue to “UPS Electrical Connections” on page 38. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Installation of the RPO function must be carried out in compliance with applicable regulations. The cable is not included. In order to fully de-energize devices and the Eaton 9135 with the RPO port, it is necessary to: Use a two-position switch (normally-open or normally-closed contact and held more than one second).
Capacity for ground/ 10 AWG). earthing conductor Continue to the following section, “Connecting the Power Cables (EU Models),” or to “Connecting the Power Cables (U Models)” on page 42. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
C A U T I O N Always connect the ground/earthing wire first. Insert the output cable through the output cable opening. Connect the three wires to the output terminal block. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 47
Install the cord-retention brackets to secure the cords and provide strain relief. (2) 16A Receptacles (4) Priority Receptacles (4) Non-Priority Receptacles Cord-Retention Brackets Figure 23. Connecting the Power Cords (EU Models) 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
C A U T I O N Always connect the ground/earthing wire first. Insert the output cable through the output cable opening. Connect the three wires to the output terminal block. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 49
C O N N E C T O 1 8 0 2 0 0 − − 2 5 0 V ~ , 2 Figure 26. Connecting the Power Cords (U Models) 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
INSTALLATION UPS Rear Panels This section shows the rear panels of the Eaton 9135 models. (2) Sets of 2 Programmable, 10A Receptacles (4) 10A Receptacles Output Terminal Block Input Terminal Block (2) 16A Receptacles 12A Thermal Switch EBM Battery Connector...
Page 51
Output Terminal Block Input Cord with L6-30P EBM Battery Connector Communication Bay Relay Port USB Port RPO Port RS-232 Port EBM RJ-11 Connector Figure 28. 5000/6000 VA, U Models 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
On/Off Button Figure 29. UPS Control Panel NOTE The On/Off button controls only the UPS output. The On/Off button has no effect on equipment connected to the UPS. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
To turn on the UPS without using utility power, press and hold the button for three seconds. The UPS starts up in Battery mode and supplies battery power to your equipment. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the OFF position. Operating Modes The Eaton 9135 front panel indicates the UPS status through the UPS indicators. Figure 30 shows the UPS front panel indicators and controls. On Battery Indicator...
End of backup time: all indicators turn off. The alarm beeps continuously and the UPS displays End of backup time Battery low. When utility power is restored after the UPS shuts down, the UPS automatically restarts. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Access to Maintenance To access the Maintenance menu: Scroll to the Maintenance menu by pressing the button. Press the button to get access. Figure 33. Access to Maintenance 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
LCM displays messages on the UPS front panel and through the communication channels, at every important stage of the UPS’s life. Press the button to display LCM warning details. Figure 34. LCM Warning Screen 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
To disable all LCM messages, select disable all while in the LCM menu. Be careful: if you disable all LCM messages, you will not be aware of any LCM events that can happen on the UPS. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Communication ports Network Management Card Load segments (PowerShare) Communication Ports The Eaton 9135 provides three communication methods that can be used simultaneously: RS-232 or USB communication. Compatible with most power management software applications. Note that both ports cannot be used at the same time.
Connect the other end of the USB cable to the USB port on your computer. USB Port Figure 35. The USB Port Install the LanSafe Power Management Software and USB drivers according to the instructions provided at www.eaton.com/powerquality. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Not used Remote Power-off signal (5–27 Vdc, 10 mA max) Operation on mains (not on battery) User common Operation on automatic bypass Low Battery Load protected Operation on battery 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Remove the slot cover secured by two screws. Insert the communication card into the slot. Secure the card with both screws. Communication Card (restricted access) Figure 37. Network Management Card (EU Model Shown) 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Replace the faulty power module with one of the same power rating (5000 VA or 6000 VA) and secure with the power module brackets. Replace the UPS front cover. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Figure 40. Removing the Battery Tray Replace the battery tray and secure with the battery retaining brackets. NOTE To ensure safety and high performance, use only batteries supplied by Eaton. Replace the UPS front cover. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
12 kg (26.5 lb) (7.8” 5” 23.7”) 214.5 498 mm UPS Internal Battery 30.5 kg (67.2 lb) (8.4” 4.6” 19.6”) 444.5 130.6 650 mm 70.5 kg (155.4 lb) (17.5” 5.1” 25.6”) 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Page 74
6000 VA 4 min 17 min 33 min 50 min 1 hr 7 min NOTE Battery times are approximate and vary depending on the load configuration and battery charge. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
NOTE In case of ”LCM WARNING”, see “Life Cycle Monitoring” on page 55. Escape Down Enter Figure 41. Troubleshooting LED 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
Call the Help Desk. Replace the battery tray test. Use ”Enter” button to display details. (see page 64). FRAME FAULT Internal chassis fault detected. Use ”Enter” Call the Help Desk. button to display details. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. Help NOTE For critical applications, immediate replacement may be available. Call the Desk for the dealer or distributor nearest you. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Eaton 9120, 9125, 9130, 9135, 9140, and FERRUPS up to 3.1 kVA Products (individually and collectively, the “Product”) purchased on or after June 1, 2004, and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
Page 80
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. 164201726 Rev 3 www.eaton.com/powerquality Eaton 9135 Two-in-One UPS (5000/6000 VA) User's Guide...
This load protection guaranty (this “Guaranty”) applies only to the original End-User (the “End-User”) of any Eaton 3105, 5110, 5115, 5125, 5130, 9120, 9125, 9130, 9135, 9140, 9150, 9155, 9170+, and FERRUPS Products (individually and collectively, the “Product”) and cannot be transferred. This Guaranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
Page 82
In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Eaton product sales or service representative. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.