Pgm Output Attributes - DSC CLASSIC PC585 Installation Manual

Software version 2.3 / dls-1 v6.7 and up
Hide thumbs Also See for CLASSIC PC585:
Table of Contents

Advertisement

NOTE:This output will activate for silent and audible alarms or
medical conditions only. It will not activate during pre-alert or
delays.
If attribute [8] is turned ON, the output will activate for the
number of seconds programmed in the PGM output timer
(section [164]).
If attribute [8] is turned OFF, in the armed state, the output will
deactivate only once the system is disarmed. If an alarm acti-
vates this output in the disarmed state, the output will deacti-
vate if a user enters a valid access code while the Bell Cut-off
timer is counting down. The output will also deactivate if
someone arms the system after the Bell Cut-off has expired.
This output can be used to indicate that an alarm has
occurred before entering the premises.
The PGM attributes for this option, programmed in Sections
[141] to [142], differ from the standard selection of attributes.
Program which events will activate the output by selecting
some or all of the following attributes:
Attribute
[1]......... Burglary (Delay, Instant, Interior, Stay/Away and
24 Hour Burglary Zones)
[2]......... Fire (Fire Keys, Fire Zones)
[3]......... Panic (Panic Keys and Panic Zones)
[4]......... Medical (Auxiliary Keys, Medical and Emergency
Zones)
[5]......... Supervisory (Supervisory, Freezer and Water
Zones)
[6]......... Priority (Gas, Heat, Sprinkler and 24 Hour Latch-
ing Zones)
[7]......... Holdup (Holdup zones)
[8]......... Output Follows Timer (output will activate for the
number of seconds programmed in the PGM Out-
put Timer) / Output Latched
NOTE:If attribute [8] is turned ON, attributes [1-7] must also be
turned ON.
PGM Output Timer. . . . . . . . . . . . . . . . . . . . . . . Section [164]
[11] System Tamper (All Sources)
The PGM output will activate when any tamper condition is
present and will deactivate when all tampers are restored.
[12] TLM and Alarm
The PGM output activates when the system experiences both
a telephone line trouble and an alarm. When the system is
armed, the output will deactivate only if an access code is
entered or if the telephone line is restored.
If an alarm activates this output in the disarmed state, the out-
put will deactivate if a user enters a valid access code while
the Bell Cut-off timer is counting down, or if the telephone line
is restored. The output will also deactivate if someone arms
the system after the Bell Cut-off has expired.
NOTE:This output will activate for all silent and audible alarms
except the Duress alarm.
[13] Kissoff Output
The output will activate for two seconds after the control panel
receives the kissoff transmission from the central station.
[14] Ground Start Pulse
The PGM Output will activate for two seconds to obtain a dial
tone on Ground Start telephone equipment before the panel
attempts to dial. Insert two 2-second pauses at the beginning
of the telephone number when using this option.
22
[15] Remote Operation (DLS-1 Support)
This output can be activated and deactivated remotely using
the DLS software.
[16] LINKS1000 Support (PGM1 Only)
The PGM output will be used as a data wire to communicate
telephone number information for the LINKS1000 cellular unit.
[17] Away Armed Status
When the system is armed in the Away mode, the PGM output
will activate at the beginning of the exit delay. The output
deactivates when the panel is disarmed.
[18] Stay Armed Status
When the system is armed in the Stay mode, the PGM output
will activate at the beginning of the exit delay. The output
deactivates when the panel is disarmed.
[19] [*][7][1] Command Output Option #1
[20] [*][7][2] Command Output Option #2
These outputs are user-initiated by entering [*][7][1-2] at any
keypad. When any output is activated, three acknowledgment
beeps are sounded.
NOTES on Option [20] [*][7][2]:
Press [*][7][2][Access Code, if required] to activate any out-
put programmed as one of PGM output option [03] or [20].
Traditionally, [*][7][2] has been reserved for resetting smoke
detectors. Smoke detectors should now be programmed as
output [03] "Sensor Reset".
NOTE:Only ONE of options [03] Sensor Reset and [20] [*][7][2]
Command Output Option #2 may be programmed on the same
system.
[21]-[24] For future use

PGM Output Attributes

In addition to programming the output type, you must also
program the PGM output attributes for each output.
PGM output options [09] "System Trouble" and [10] "System
Event" have their own unique set of attributes listed below the
description of each output type.
PGM output options [01], [03], [05]-[08], [11]-[20] have the
following attributes:
Attribute ....ON
[1] .......PGM Enable
[3] .......True Output
Attribute ON: the output energizes when activated
Attribute OFF: the output de-energizes when acti-
vated
[4] .......Output Pulsed
Attribute ON: the output will activate once for the
amount of time programmed in section [164]
when initiated by the user
Attribute OFF: the output will toggle ON or OFF
when initiated by the user.
(Only applicable to options [19]-[20].)
[5] .......Access Code Req. No code Req.
Attribute ON: the output requires a code for acti-
vation.
Attribute OFF: no code required.
(only applicable to keypad-activated outputs)
PGM attributes return to their default settings when you
change PGM output options. Please see the programming
worksheets for a list of the default settings for each PGM out-
put type.
OFF
PGM Disable
Inverted Output
Output ON/OFF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Classic pc585

Table of Contents