Timebase; Resetting Factory Defaults; Installer's Lockout; Walk Test (Installer) - DSC CLASSIC PC585 Installation Manual

Software version 2.3 / dls-1 v6.7 and up
Hide thumbs Also See for CLASSIC PC585:
Table of Contents

Advertisement

Solution: Program the panel to adjust the clock by 51 sec-
onds (instead of the default 60 seconds) for the last minute of
each day in section [700]. This will speed up the panel's clock
by 9 seconds, correcting the problem.
Example #2: The clock gains an average of 11 seconds per
day.
Solution: Program the panel to adjust the clock by 71 sec-
onds (instead of the default 60 seconds) for the last minute of
each day in section [700]. This will slow down the panel's
clock by 11 seconds, correcting the problem.
NOTE:If the Auto-arm time is set for 23:59, any change to the
Clock Adjust option will directly affect the Auto-arm pre-alert
time.
Clock Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [700]

5.29 Timebase

In cases of unstable AC power input you can use the internal
crystal to keep a more accurate timebase by enabling the
Timebase is Internal Crystal option.
If the 50 or 60Hz AC power input is very stable it can be used
as the timebase, by enabling the Timebase is AC line option.
Timebase Internal Crystal/AC line . . . . . . . Section [701]: [2]

5.30 Resetting Factory Defaults

On occasion, it may be necessary to default the main control
panel or one of the connected modules: the LINKS2X50 Radio
interface, the PC5132 wireless receiver, and the PC5400
Printer module.
To default the main control panel (hardware), perform the fol-
lowing:
1. Remove AC and battery from the panel.
2. Remove all wires from the Zone 1 and PGM1 terminals.
3. With a piece of wire short the Zone 1 terminal to the PGM1
terminal.
4. Apply AC power to the main panel.
5. When Zone Light 1 is lit on the keypad the default is com-
plete.
6. Remove AC power from the control
7. Reconnect all original wiring and power up the control.
NOTE: AC power must be used to power the panel. The panel
will not default if only the battery is used.
To default the main control panel software and other modules,
perform the following:
1. Enter the Installer's Programming mode.
2. Enter the appropriate programming section [XXX].
3. Enter the Installer's Code.
4. Re-enter the appropriate programming section [XXX].
The panel will take a few seconds to perform the default.
When the keypad is again operational the default is complete.
NOTE:If using Identified Wireless Keys (PC5132 v3.0 or later
only), when the main panel is defaulted, all wireless key
access codes must be re-programmed. Refer to your PC5132
v3.0 Installation Manual for more information.
Restore Alternative Communicator
(LINKS2X50)
to Default Programming. . . . . . . . . . . . . . . . . . Section [993]
Restore PC5132 to Default Programming . . . . Section [996]
P r o g r a m
D e s c r i p t i o n s :
Restore PC5400 Printer to Default ProgrammingSection [997]
Restore Panel to Default Programming . . . . . . . Section [999]

5.31 Installer's Lockout

If Installer's Lockout is selected, a hardware default cannot
be performed. If a software default is performed, all program-
ming will restore to factory default.
If Installer's Lockout Disable is selected, the panel will
restore all programming to factory defaults when a hardware
or software default is performed on the main control panel.
To enable or disable Installer's Lockout, perform the following:
1. Enter the Installer's Programming mode.
2. Enter the appropriate programming section: [990] or [991].
3. Enter the Installer's Code.
4. Re-enter the appropriate programming section: [990] or
[991].
Installer Lockout Enable . . . . . . . . . . . . . . . . . . Section [990]
Installer Lockout Disable . . . . . . . . . . . . . . . . . . Section [991]

5.32 Walk Test (Installer)

The Installer Walk Test can be used to test the alarm state of
each zone of the panel. The walk test cannot be used to test
zone type [24].
Before beginning the walk test, ensure the following condi-
tions are met:
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]:
[3])
3. The Fire Bell is Continuous option is disabled (section
[014]: [8])
4. The Transmission Delay is disabled, if Transmission
Delay is not required (section [370])
NOTE: Fire Troubles are not supported in Walk Test.
To perform a walk test:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Out-
put for two seconds, log the event to the event buffer and
communicate the alarm to central station.
Test each zone several times. Check the event buffer to
ensure that all zones and FAP keys are functioning properly.
NOTE: Zones with the Force Arm attribute enabled, will not
cause the Ready light to go out when they are violated.
To stop the test:
Step 1 - Enter Installer Programming
Step 2 - Enter section [901]
NOTE:The alarm memory is cleared upon entering Walk Test
mode. When the walk test is complete, the Alarm Memory light
will remain lit, but there will be no alarms in memory. The light
will turn off the next time the panel is armed.
Installer Walk Test Enable/Disable. . . . . . . . . . . Section [901]
5 . 2 9
T i m e b a s e
27