Omron SYSDRIVE 3G3JV Setup Manual page 55

Compact simplified inverters
Hide thumbs Also See for SYSDRIVE 3G3JV:
Table of Contents

Advertisement

List of Parameters
Param-
Name
eter
No.
(Regis-
ter No.
(Hex))
n55
Stall pre-
vention
(0137)
during de-
celeration
n56
Stall pre-
vention
(0138)
level dur-
ing accel-
eration
n57
Stall pre-
vention
(0139)
level dur-
ing opera-
tion
n58
Frequency
detection
(013A)
level
n59
Overtor-
que detec-
(013B)
tion func-
tion selec-
tion
n60
Overtor-
que detec-
(013C)
tion level
n61
Overtor-
que detec-
(013D)
tion time
Description
Used to select a function to change the decel-
eration time of the motor automatically so that
there will be no overvoltage imposed on the
motor during deceleration.
0: Stall prevention during deceleration enabled
1: Stall prevention during deceleration dis-
abled
Used to select a function to stop the accelera-
tion of the motor automatically for stall preven-
tion during acceleration.
Set the level in percentage based on the rated
current of the Inverter as 100%.
Used to select a function to reduce the output
frequency of the Inverter automatically for stall
prevention during operation.
Set the level in percentage based on the rated
current of the Inverter as 100%.
Used to set the frequency to be detected.
Note The parameter n40 for multi-function
output must be set for the output of fre-
quency detection levels 1 and 2.
Used to enable or disable overtorque detec-
tion and select the processing method after
overtorque detection.
0: Overtorque detection disabled
1: Overtorque detection only when speed coin-
cides and operation continues (issues
alarm)
2: Overtorque detection only when speed coin-
cides and output shut off (for protection)
3: Overtorque always detected and operation
continues (issues alarm)
4: Overtorque always detected and output
shut off (for protection)
Used to set overtorque detection level.
Set the level in percentage based on the rated
current of the Inverter as 100%.
Used to set the detection time of overtorque.
Chapter 3
Set-
Default
Changes
ting
setting
during
range
opera-
tion
0, 1
0
No
30 to
170
No
200
30 to
160
No
200
0.0 to
0.0
No
400
0 to 4
0
No
30 to
160
No
200
0.1 to
0.1
No
10.0
Memo
3-15