List of Parameters
Param-
Name
eter
No.
(Regis-
ter No.
(Hex))
n40
Multi-func-
tion output
p
(0128)
(0128)
(MA/MB
and MC
output ter-
minals)
minals)
3-12
Description
Used to select the functions of multi-function
output terminals.
Set
Function
val-
ue
0
Fault output ON: Fault output (with
protective function work-
ing)
1
Operation
ON: Operation in prog-
in progress
ress
2
Frequency
ON: Frequency detection
detection
(with frequency reference
coinciding with output fre-
quency)
3
Idling
ON: Idling (at less than
min. output frequency)
ON: Output frequency y
4
Frequency
detection 1
frequency detection level
(n58)
ON: Output frequency x
5
Frequency
detection 2
frequency detection level
(n58)
6
Overtorque
Output if any of the fol-
being moni-
lowing parameter condi-
tions is satisfied.
tored (NO-
contact out-
n59: Overtorque detec-
put)
tion function selection
n60: Overtorque detec-
tion level
n61: Overtorque detec-
61 O
7
Overture
tion time
being moni-
tored (NC-
NO contact: ON with
contact out-
overtorque being
put)
detected
NC contact: OFF with
overtorque being
detected
8
Not used
---
9
10
Alarm out-
ON: Alarm being de-
put
tected (Nonfatal error be-
ing detected)
11
Base block
Base block in progress
in progress
(in operation with output
shutoff)
12
RUN mode
ON: Local mode (with the
Digital Operator)
Set-
ting
range
0 to 7,
10 to
0
18
Description
d
Chapter 3
Default
Changes
Memo
setting
during
opera-
tion
1
No

Hide quick links: