List of Parameters
Parameter
Name
No. (Reg-
ister No.
(Hex))
n09
Maxi-
mum
(0109)
frequen-
cy
(FMAX)
n10
Maxi-
mum
(010A)
voltage
(VMAX)
n11
Maxi-
mum
(010B)
voltage
frequen-
cy (FA)
n12
Middle
output
(010C)
frequen-
cy (FB)
n13
Middle
output
(010D)
frequen-
cy volt-
age
(VC)
n14
Mini-
mum
(010E)
output
frequen-
cy
(FMIN)
n15
Mini-
mum
(010F)
output
frequen-
cy volt-
age
(VMIN)
n16
Accel-
eration
(0110)
time 3
n17
Decel-
eration
(0111)
time 3
n18
Accel-
eration
(0112)
time 4
n19
Decel-
eration
(0113)
time 4
3-4
Description
Used to set the V/f pattern as the ba-
sic characteristic of the Inverter with
output voltage per frequency set.
Output
voltage
n10
(VMAX)
n13
n13
(VC)
n15
(VMIN)
0
n14
n12
n11
(
(FMIN)
) (
(FB)
)
(
(FA)
)
Note Set the parameters so that
the following condition will be
satisfied.
n14 x n12 < n11 x n09
14 x 12
11 x 09
Note The value set in n13 will be
ignored if parameters n14 and
n12 are the same in value.
Acceleration time: The time required
to go from 0% to 100% of the maxi-
mum frequency.
Deceleration time: The time required
Deceleration time: The time required
to go from 100% to 0% of the maxi-
mum frequency.
Note The actual acceleration or de-
celeration time is obtained
from the following formula.
Acceleration/Deceleration time
= (Acceleration/Deceleration
= (Acceleration/Deceleration
time set value) × (Frequency
reference value) ÷ (Max. fre-
quency)
Setting
range
50.0 to
400
1 to 255
0.2 to 400
Fre-
quency
(Hz)
n09
(
(FMAX)
)
0.1 to 399
1 to 255
0.1 to 10.0
1 to 50
(see note
2)
0.0 to 999
Chapter 3
Default
Changes
setting
during
opera-
tion
60.0
No
200
No
60.0
No
1.5
No
12
No
1.5
No
12.0
No
10.0
Yes
10.0
Yes
10.0
Yes
10.0
Yes
Memo