Design

1-2-2 Standard Connections

Single-phase 100 V AC
Forward/Stop
Multi-function input 1 (Reserve/Stop)
Multi-function input 2 (S3) (Fault Reset)
Multi-function input 3 (S4) (External fault
Normally open)
Multi-function input 4 (S5) (Multi-step speed
reference 1)
Sequence input common
Frequency reference power
supply 20 mA at +12 V
Frequency reference input
FREQ
adjuster
Frequency reference common
(2 kΩ, 1/4 W min.)
Note 1. The braking resistor cannot be connected because no braking transistor is incorporated.
Note 2. A DC Reactor can be connected in series between the R input and L1 terminal or between the
S input and L2 terminal to use it as an AC reactor.
D DC Reactor Wiring Example
Single-phase 100 V AC
Applicable Noise Filters
Inverter
3G3JV-A1001
3G3JV-A1002
Applicable DC Reactors
Inverter
3G3JV-A1001
3G3JV-A1002
1-10
DC reactor
(optional)
Noise Filter
Applicable Filter
3G3JV-PRS1010J
(for either 0.1 kW or 0.2 kW)
(f
i h
0 1 kW
Applicable Reactor
3G3HV-PUZDAB5.4A8MH
3G3HV-PUZDAB18A3MH
Noise Filter
DC Reactor
10 A at 250 V AC, single-phase
0 2 kW)
5.4 A, 8 mH
18 A, 3 mH
Chapter 1
3-phase 200 V AC
Multi-function contact output
NO
NC
Common
Analog monitor output
Analog monitor output common
Specifications
,
g
p
Specifications