A-4 CP1L Programming Examples

A-4-9 Exchanging Data between CP1Ls

Functions Used
Simple PLC Link
Operation Overview
A
System Configuration
Wiring Example
160
SYSMAC CP1L Getting Started Guide
By using RS-422A/485 option boards, up to 10CH of data per CPU unit can be shared
by as many as 9 CP1L/CP1H/CJ1M units, without the aid of a program.
Current temperature information is exchanged by boilers.
This setup may be used to adjust boiler temperatures according to the other boiler
conditions, or to monitor the boilers from a single location.
Boiler A
Boiler B
Boiler A: CP1L (Master)
Temperature sensor unit
CP1W-TS101
COMM
RDA - RDB+ SDA - SDB+ FG
1CH,2CH
2 Pt100 sensor inputs
CP1W-CIF11
(RS422/485 option board)
CP1W-CIF11
1
RDA–
2
RDB+
3
SDA–
Simple PLC link
4
SDB+
5
FG
Boiler C
Boiler B: CP1L (Slave No.0)
Temperature sensor unit
CP1W-TS101
COMM
RDA - RDB+ SDA - SDB+ FG
1CH,2CH
2 Pt100 sensor inputs
CP1W-CIF11
(RS422/485 option board)
CP1W-CIF11
RDA–
1
RDB+
2
SDA–
3
SDB+
4
FG
5
Boiler C: CP1L (Slave No.1)
Temperature sensor unit
CP1W-TS101
COMM
RDA - RDB+ SDA - SDB+ FG
1CH,2CH
2 Pt100 sensor inputs
CP1W-CIF11
(RS422/485 option board)
CP1W-CIF11
RDA–
1
RDB+
2
SDA–
3
SDB+
4
FG
5