Indicator Statuses
This section describes the operating statuses of CP1L as displayed by the
operation indicators.
POWER
(Green)
RUN
(Green)
ERR/ALM
(Red)
INH
(Yellow)
PRPHL
(Yellow)
BKUP
(Yellow)
Lit
Power is ON.
Not lit
Power is OFF.
Lit
CP1L is executing a program in either RUN or MONITOR mode.
Not lit
Operation is stopped in PROGRAM mode, or stopped due to a fatal error.
Lit
A fatal error (including FALS execution) or a hardware error (WDT error)
has occurred.
CP1L operation will stop, and all outputs will be turned OFF.
Blinking
A non-fatal error (including FAL execution) has occurred.
CP1L operation will continue.
Not lit
Operation normal.
Lit
The output OFF bit (A500.15) has turned ON.
All outputs will be turned OFF.
Not lit
Operation normal.
Blinking
Communication (either sending or receiving) is active on the peripheral
USB port.
Not lit
Any other state.
Lit
• User program, parameter, or data memory is being written to or read
from the built-in flash memory (backup memory).
• User program, parameter, data memory, DM defaults, or comment
memory is being written to or read from the memory cassette.
• User programs, parameters, and data memory are being restored
following a PLC power-on.
Note: Do not turn the PLC power supply OFF while this indicator is lit.
Not lit
Any other state.
1-2 Part Names and Functions