By observing the two LED indicators and the Outputs Enable Switch lamp, and observing
PDU operation, you can troubleshoot PDU problems. Table 6 assumes that the Outputs Enable
Switch is in the On position.
Table 6. Troubleshooting From the LEDs
Yellow
Green
Switch
LED
LED
Lamp
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
If the outputs of the PDU are being switched off often due to sags (low-line conditions), you
should take action to correct the mains. One source of information that explains how to reliably
measure the mains and correct low-line problems is a power primer called Why Peak
Measurements are More Reliable then RMS Measurements (HP E4000-90037, December 1995),
available through your HP representative.
HP E1135C POWER DISTRIBUTION UNIT Rev. C
34
Switched
Problem
Outputs
OFF
No line voltage (mains) is present
OFF
Yellow LED is open
ON
Outputs Enable Switch lamp is open
ON
NORMAL OPERATION
OFF
Line voltage went greater then 135/270 Vac
(surge) or S1 is set to the wrong position
OFF
Line voltage went less than 85/170 Vac
(sag) or S1 is set to the wrong position