WIRING THE AC MAINS AND LOADS TO THE PDU

WIRING THE AC MAINS AND LOADS TO THE PDU
These procedures must be performed only by trained and qualified service
personnel.
To prevent the possibility of electrical shock, which could cause injury or
death, connect an ac mains ground wire to the "GND" terminal of the
Mains Disconnect Switch inside the PDU.
Holes are provided in the front, side and rear covers for wire egress. For
safety, use strain relief cable clamps (0400-0377) on all wires. Install
filler plugs (6960-0177) in all unused holes.
After wiring the ac mains inputs to the PDU, turn on the PDU and
measure the outputs using a voltmeter to verify that they are at the
expected voltage before wiring the loads.
For electrical safety, do not connect more than one wire to a terminal on
the output terminal block. Each terminal has two terminations on the
terminal block. See Figure 3, page 5.
|
HP E1135C POWER DISTRIBUTION UNIT Rev. C
22
WARNING