Connecting A Pigtail To The E1135C Pdu - HP E1135C Operating And Service Manual

Table of Contents

Advertisement

WIRING THE AC MAINS AND LOADS TO THE PDU

Connecting a Pigtail to the E1135C PDU

|
|
The E1135C PDU is the replacement for the E1131A, and E1135A/B PDUs. The input
terminals on the E1135C on the mains disconnect switch easily fit wire size 10 square
|
|
millimeters (#8 AWG). It is strongly suggested that if the recommended wire size in the
|
following is greater than 10 square millimeters (#8 AWG , that an 450 millimeters (18-inches)
|
to 609 millimeters (24-inches) pig tail be created using 10 square millimeters (#8 AWG) wire,
|
and the recommended larger cable be connected to the pigtail as shown in Figure 21.
|
|
|
|
|
AC Source Voltage
|
|
|
|
|
|
|
|
Breaker
|
Box
|
|
|
|
|
|
|
|
|
|
Figure 21. Using a Pigtail with the E1135C PDU
|
|
|
HP E1135C POWER DISTRIBUTION UNIT Rev. C
32
Power
Receptacle
Added Power Receptacle on a short pigtail if an
E1135C PDU is used and the existing wire size of
the power drop exceeds 10
HP 3X7X System
PDU
2
mm (#8 AWG).
Pigtail.wpg