Physical Description

The PDU occupies three EIA
(5.25 inches) high, 368 millimeters (14.5 inches) wide, and 152 millimeters (6 inches) deep. The
PDU weighs 4.4 kilograms (9.6 pounds). The color is graphite gray.

Operating Voltages

Table 1 lists the operating voltages (ac mains) of the PDU and indicates the pages that
describe how to connect the different mains configurations to the PDU. The nominal operating
frequencies are 50 or 60 hertz.
Table 1. HP E1135C PDU Operating Voltages
2
Input Voltage
120/208–240/415 V 3-Phase Wye with Neutral
208 or 220 V 3-Phase Wye
100/200–120/240 V Three-Phase Delta
120/208–240/415 V Single Phase Wye with Neutral
100/200–120/240 V Single Phase with Center-Tap Neutral
200–240 V Single Phase Non-Earthed
100–240 V Single Phase Earthed
1
Conforms to Electronics Industries Association standard EIA-310-C. One EIA unit occupies 1.75
inches (44.5 millimeters) of vertical rack space.
2
All voltages are nominal rms values. Voltages are listed in order of preference: the higher the mains
voltage, the lower the mains current. Three-phase power is the most efficient.