120/208–240/415 V 3-Phase Wye with Neutral
Figure 14. Wiring the Mains: 120/208
The line-to-neutral voltage must not exceed 240 volts. The voltage
between any two lines (line-to-line) may be as high as 415 volts.
Tools for connecting the mains and loads:

1/4-inch flat blade screwdriver for the Mains Disconnect Switch

1/8-inch flat blade screwdriver for the Output Terminal Block
Set the Voltage Selector Switch (S1) on the Control Board to 230V (page 9).
Wiring Loads: If the line-to-line voltage is greater than 250 volts, wire loads line-to-neutral
only. If the line-to-line voltage is less than 250 volts, wire either line-to-line
(full voltage) or line-to-neutral.
WIRING THE AC MAINS AND LOADS TO THE PDU
L1
L2
L3
1
0
G
T1
T2
T3
G
L1 L2 L3 N*

240/415 V 3-Phase Wye with Neutral
NOTE
HP E1135C POWER DISTRIBUTION UNIT Rev. C
N
N
10A 10A
MAINS5.WPG
25
|
|
|