OPERATING DESCRIPTIONS

The PDU comes from the factory with the rear panel receptacles (outlets) wires cable tied
together; not connected internally (page 6). The installer of the PDU must connect the receptacle
circuits as needed. Depending on the type of PDU ordered, the receptacle circuits will come
wired as two circuits with four receptacles per circuit or four circuits with two receptacles per
circuit. Also, the PDU may or may not include an Output Enable Switch; it is not included in
units when a remote Output Enable Switch is being used.
HP Part
2 Receptacle Circuits
Number
4 Receptacles per
E1135-80050
E1135-80052
E1135-80053
E1135-80054
|
|
|
E1135-80056

Where to Get Help

|
If you need technical assistance with this product, contact HP's Measurement Systems
|
Knowledge Center (MSKC). In the U.S. call 1-800-593-6635 with your MSKC support handle.
|
Outside the U.S. call your local HP Service Representative to access the MSKC.
OPERATING DESCRIPTIONS

The Outputs Enable Switch

The Outputs Enable Switch switches ac mains power to the Control Board. The Control
Board monitors the ac mains voltage and if it is within acceptable limits, it closes the 4-pole
contactor, energizing the output terminal block. The Outputs Enable Switch can be removed from
the front panel of the PDU and located elsewhere around a system (see "Wiring a Remote Outputs
enabled switch" below).
HP E1135C POWER DISTRIBUTION UNIT Rev. C
12
Table 3. HP E1135C PDU Product Matrix
4 Receptacle Circuits
2 Receptacles per
Circuit
X
X
Output Enable
Switch Included
Circuit
X
No
X
Yes
Yes
X
Yes
No