If you are replacing an E1131A or E1135A/B PDU, either wire it like the
existing PDU, or use the documentation that came with your product.
You will connect the mains to the Mains Disconnect switch instead of the
input block, but the T1, T2, T3 terminals match the L1, L2, L3 terminals
of the previous PDU. There are fewer terminals on the output block of the
E1135C, but the labels are the same.

Stripping Wires and Torqueing Terminals

To ensure that all input and output wires are safely connected in the PDU, strip the wires and
torque the terminal screws as shown in Table 5.
Table 5. Stripping and Torqueing Specifications
Terminals
Mains Disconnect terminals:
— T1, T2, T3, NEU, GND
Input block terminals:
— 10A terminals
— LL1, LL2, NEU, GND
Output block terminals:
— L1, L2, L3, NEU, GND

Tools Needed


T10 Torx driver for removing covers (access plates)

1/4-inch flat blade screwdriver for connecting the ac mains

1/8-inch flat blade screwdriver for connecting loads
1
Units of torque: "N-m" means newton-meters; "in-lb" means inch-pounds.
WIRING THE AC MAINS AND LOADS TO THE PDU
NOTE
Strip Wires
15 mm (0.6 in)
15 mm (0.6 in)
8 mm (0.3 in)
8 mm (0.3 in)
HP E1135C POWER DISTRIBUTION UNIT Rev. C
1
Torque Terminals
1.7 N-m (16 in-lb)
2.0 N-m (18 in-lb)
0.68 N-m (6 in-lb)
0.5 N-m (4.4 in-lb)