Specifications

Table 2. Specifications of the HP E1135C PDU
Input Voltage:
Input Current:
Input Wire Size:
Mains Disconnect:
Output Voltage:
Output Current:
Main/Branch PDU drive: Can control up to 20 other E1135 PDUs
Operational Altitude:
Operational Temperature: 40 degrees C max
Operational Humidity:
Transients:
Pollution degree:
The HP E1135C PDU is intended for indoor use only; DO NOT use it outdoors. The PDU
conforms to the European Community Machinery Directive. There are no preventive maintenance
requirements for the PDU. To clean the outer surface of the PDU, use a clean dry cloth.

PDU Product Matrix

The HP E1135C PDU is available under several different HP part numbers to reflect different
configurations — as shipped from the factory — which are used by both HP and non-HP
manufacturers. These configurations are shown in Table 3.
1
American Wire Gauge.
2
If greater than 10 square millimeters (#8 AWG) wire size is required due to loading, a pigtail is
required. See "Connecting a Pigtail to the E1135C PDU" on page 32.
100–240 volts single phase, 200–415 volts 3-phase, 50/60 hertz
32 amps max
On the Mains Disconnect Switch:
1
#8 AWG
10 square millimeters (0.147-inch, 3.57 mm dia.)
2
max wires
600 volts, 60 amps, 4-pole, lockable
240 volts max
From the output terminal block:
15 amps max per branch circuit (10 circuits)
From the outlets (receptacles):
15 amps max per circuit if switched (circuit breakers) or
10 amps max per circuit if un-switched (fuses)
2,000 meters (6,560 feet) max
80 percent R.H. max
4,000 volts peak max (IEC installation category III)
2
HP E1135C POWER DISTRIBUTION UNIT Rev. C
|
|
|
|
11