P3.06
minimum fan speed
P3.07
maximum fan speed
P3.08
slow ignition
P3.09
maximum fan speed - heating
P3.13
reignition speed
ƒ enter the sub-menu by pressing
ƒ set the required values with the
referring to the following tables
ƒ make sure P3.09=P3.10
table 1
MAXIMUM NO. FAN
METHANE GAS
ROTATIONS
(G20)
35 Risc.
7.300
45 Risc.
9.100
table 2
MINIMUM NO. FAN
METHANE GAS
ROTATIONS
(G20)
35
45
table 3
NO. FAN ROTATIONS
METHANE
(SLOW IGNITION)
GAS (G20)
4.000
35
4.000
45
ƒ confirm the values with

3.19 Gas valve calibration

Run the CO
check procedure as explained in paragraph
2
"3.17 Combustion check". If the values need to be
modified, proceed as follows:
ƒ check the CO
values with the casing closed
2
ƒ remove the casing as explained in paragraph "2.10
Removing the casing"
ƒ check the CO
values again, with the casing open
2
ƒ bearing in mind the difference between the values
measured with the casing closed and open, if nec-
essary adjust the CO
to the value shown in the table
2
- (minus) the difference noted. Example:
ƒ CO
value measured with the casing closed = 8.5%
2
ƒ CO
value measured with the casing open = 8.3%
2
ƒ value to be set for CO
ƒ value that must be measured for CO
closed = 9.0%
ƒ for the CO
value adjustments:
2
ƒ rotate the maximum output adjustment screw clock-
wise to reduce the value, or anti-clockwise to in-
crease it
ƒ rotate the minimum output adjustment screw clock-
wise to increase the value, or anti-clockwise to re-
duce it
ƒ with the casing open, and after adjusting the CO
ue at the minimum output, check the CO
maximum output again
ƒ after completing the adjustments, refit the casing and
check the CO
value corresponds to the one shown in
2
the table
CO
+
2
Minimum output
adjustment screw
and
buttons,
LIQUID GAS
(G31)
7.100
8.900
LIQUID GAS
(G31)
1.750
1.650
1.750
1.650
LIQUID
GAS (G31)
4.000
4.000
Enter
.
with casing open = 8.8%
2
with casing
2
value at the
2
CO
2
Maximum output
adjustment screw

3.20 Gas conversion

It is easy to make the conversion from one gas to another
even after the boiler has been installed. This operation
must be carried out by professionally qualified personnel.
The boiler is designed to operate with methane gas (G20)
according to the product label. It is possible to convert
the boiler to LPG with the aid of the relative kits.
For disassembly refer to instructions below:
ƒ disconnect the boiler from the electricity supply and
turn off the gas tap
ƒ remove the casing as explained in paragraph "2.10
Removing the casing"
ƒ release the instrument panel and rotate it forwards.
ƒ Loosen the nut of the gas train (A).
ƒ Remove the nozzle (B) inside the gas valve, and re-
rpm
place it with the one in the kit.
rpm
A
rpm
rpm
B
After completing the operations:
rpm
ƒ refit the previously removed components
rpm
ƒ power the boiler and turn on the gas tap.
Adjust the boiler as explained in paragraph "3.18
Adjustments" and paragraph "3.19 Gas valve calibration".
9
Conversion must be carried out by qualified per-
sonnel.
9
After the transformation, apply the new rating
plate included in the kit.

3.21 Signalling and faults

In there is a fault, the
sec OFF). The backlight will flash for 1 min (1 sec ON, 1 sec
OFF) and then switch off, but the bell will carry on flash-
ing. The 4-digit area of the display will show a sliding
message with the error code.
val-
2
The following icons may appear when a fault arises:
lights up for a flame alarm (E010)
− RESET lights up for an alarm that needs to be manually
reset by the user (e.g. a flame lockout)
lights up along with the
lockout and water failure faults)
-
In addition, when parameter P3.02 is set with a value of
1, meaning that a water pressure transducer is fitted, the
pressure value is shown when it is higher than 5.0 bar
(excessively high pressure); the boiler carries on working
as these are merely info messages. With pressure lower
than 0.8 bar (excessively low pressure) the boiler stops
functioning. In these cases, the pressure value, with the
relative measurement unit, is also shown at the end of
the following error messages:
• E041 - E040
39
COMMISSIONING