Riello CONDEXA HPR Series Instructions For The Installer And For The Technical Assistance Centre page 31

Table of Contents

Advertisement

B23P-B53P
60-100
Ø
B
A
C
MAX LENGTH PIPES Ø80 + Ø80 CONDEXA HPR
55
50
45
40
35
30
25
20
15
10
HPR 45
5
0
0
5
10
15
20
25
30
35
Air suc�on pipe length (m)
B23P - B53P
Ø80-80
80-80
80-125
Ø
Ø
A
C
HPR 35
40
45
50
55
60
65
70
75
Ø60-100
Ø80-80
with adaptor
Ø80-125
TYPE "B" INSTALLATION
Discharge Ø 80 mm
Maximum
Model
Ø 80 mm
Condexa HPR 35
Condexa HPR 45
With type B installation, the combustion air is taken
from the room and delivered via the openings made on
the rear panel of the appliance, which must be located
in a suitable utility room that is well-aired.
TYPE "C" INSTALLATION
Concentric pipes Ø 80-125 mm
Maximum
Model
Ø 80-125 mm
Condexa HPR 35
Condexa HPR 45
Concentric pipes ø 60-100mm
Maximum
Model
Ø 60-100 mm
Condexa HPR 35
Condexa HPR 45
Separated pipes Ø 80 mm + Ø 80 mm
Maximum
Model
Ø 80+80 mm
Condexa HPR 35
30+30 m
Condexa HPR 45
9
Do not install the flue gas exhaust near flammable
or plastic materials, whose characteristics can be
changed in the presence of high temperatures.
9
The straight length is intended without bends, and
includes the terminals and joints.
9
The boiler is supplied without the flue gas/air suc-
tion kit, as it is possible to use the accessories for
condensing appliances best suited to the installation
characteristics (refer to the catalogue).
9
In the case of use of non-original flue gas exhaust
and air intake ducts, the use of certified ducts com-
pliant with the appliance to which they are connected
must still be guaranteed, with a temperature class
≥120°C and resistant to condensation.
9
To ensure the best installation safety, attach the pipes
to the wall (or ceiling) using specific fixing brackets
positioned in line with each joint (at a distance such
that the length of each single extension is not exceed-
ed) and immediately before and after every change of
direction (bend).
9
The maximum pipe length values refer to the flue pipe
accessories available in the catalogue.
9
It is compulsory to use specific pipes.
9
The non insulated flue gas outlet pipes are potential
sources of danger.
31
INSTALLATION
Pressure loss
length
bend 45° bend 90°
48 m
1 m
33 m
1 m
Pressure loss
length
bend 45° bend 90°
25 m
1 m
25 m
1 m
Pressure loss
length
bend 45° bend 90°
10 m
1,3 m
10 m
1,3 m
Pressure loss
length
bend 45° bend 90°
1 m
21+21 m
1 m
1,5 m
1,5 m
1,5 m
1,5 m
1,6 m
1,6 m
1,5 m
1,5 m