Replace The Power Zone P&L Controller; Replace The Power Zone Pro Sync Annunciators - Generac Power Systems Power Zone Pro Sync Owner's Manual

Table of Contents

Advertisement

Operation
Setup IP settings (if needed):
See
Figure
3-4. Select "Setup" (B).
7.
Select "Communications".
8.
Select "Ethernet/Wi-Fi/Bluetooth".
9.
Select the icon shown in
10.
Figure 3-8. Communications Icon
Enter necessary IP settings.
11.
Check the "Ethernet Enabled" checkbox.
12.
Select "Apply Changes" when finished to save
13.
changes.
Delete old Display from the "Device Manager" screen
on each Display, assign the new Display a Friendly
Name, and verify communication:
Connect Ethernet cable from Main Controller to the
14.
new Display.
See
Figure
3-4. Select "Setup" (B).
15.
Select "Communications".
16.
Select "Device Manager".
17.
Select "Clear Devices". Repeat this step on ALL
18.
other Displays in the system including P&L Display.
Go back to the new Display.
19.
Select the new Display entry in the list.
20.
Select "Edit".
21.
Assign a Friendly Name for this Display and select
22.
"Save".
Verify the new Display is visible in the list of
23.
devices.
Replace the Power Zone P&L Controller
Download existing P&L configuration:
See
Figure
3-4. Select "Setup" (B).
1.
Select "Modules".
2.
Select "Permissives and Loadshed Setup".
3.
Select "Download Config" at the bottom of the
4.
screen. The configuration file will be saved in your
"Documents" folder.
Replace circuit board (part no. 0L4232):
Note which Ethernet cables are plugged into which
5.
ports on the existing board by taking a picture and/
or labeling the Ethernet cables.
Replace the circuit board but ONLY plug in the
6.
Ethernet cable for the Display.
26
Figure
3-8.
010922
Upgrade the P&L board and Display firmware to the
latest version from GenService:
Upgrade firmware in the P&L board and Display to
7.
the latest version from GenService.
NOTE: Do NOT proceed until completing step 7.
Load the saved configuration file into the P&L:
See
Figure
3-4. Select "Setup" (B).
8.
Select "Modules".
9.
Select "Permissive and Loadshed Setup".
10.
Select "Upload Configuration".
11.
Select your original configuration file (.json).
12.
After the file uploads, select "Load" and verify the
13.
settings are correct.
Select "Apply Changes" at the bottom of the screen
14.
to save the settings.
Delete old P&L from the "Device Manager" screen on
each Display, assign the new P&L a Friendly Name,
and verify communication:
Plug in the remaining Ethernet cables.
15.
See
Figure
3-4. Select "Setup" (B).
16.
Select "Communications".
17.
Select "Device Manager".
18.
Select "Clear Devices". Repeat this step on ALL
19.
other Displays in the system including P&L Dis-
plays.
Select the new entry in the list of devices.
20.
Select "Edit".
21.
Enter a Friendly Name for this P&L and select
22.
"Save".
Replace the Power Zone Pro Sync
Annunciators
NOTE: If using an RS-485 connection to the annuncia-
tor, see the annunciator Owner's Manual in addition to
these instructions.
Write down setup of annunciator being replaced (if
annunciator is still able to communicate):
See
Figure
3-4. Select "Setup" (B).
1.
Select "Modules".
2.
Select "Annunciator Setup".
3.
See
Figure
3-9. Under "Remote Annunciator", use
4.
the "Select a Name" dropdown to select the annun-
ciator being replaced.
Figure 3-9. Select Annunciator
Owner's Manual for Power Zone Pro Sync
010923

Advertisement

Table of Contents
loading

Table of Contents