Troubleshooting
Alarm Display Text
FAIL START
REPLACE OIL
REPLACE OIL FILTER
REPLACE SPARK PLUG
REPLACE AIR FILTER
REPLACE BATTERY
GENERAL SERV REQ
XFER SWITCH UTIL MAINT
XFER SWITCH GEN MAINT
TASK TIMEOUT
TASK EXIT
HW OVERSPEED SHUTOFF
WATCHDOG RESET OCCURRED
CHECKSTOP RESET OCCURRED
SYSTEM RESET OCCURRED
MPS COMMS FAIL
MPS OUT OF SERVICE WARNING
MPS GEN ADDED
PLC GEN DISABLED
CURRENT PROTECTION
OVER CURRENT PROTECTION
ENGINE STALLED
STARTER NOT ENGAGED
BOSCH THROTTLE STUCK
30
Type
Alarm Description
SD
Generator failed to start after preselected
number of attempts
WN
Oil maintenance thresholds exceeded
WN
Oil Filter maintenance thresholds exceeded
WN
Spark plug maintenance thresholds exceeded
WN
Air filter maintenance thresholds exceeded
WN
Battery maintenance thresholds exceeded
WN
General maintenance thresholds exceeded
WN
Utility transfer switch maintenance thresholds
exceeded
WN
Generator transfer switch maintenance
thresholds exceeded
SD
One or more firmware tasks have timed out -
Trips E-Stop circuit
SD
Main Controller operating system task exited
unexpectedly
SD
Hardware overspeed circuit triggered - Trips E-
Stop Circuit
SD
Microcontroller watchdog timed out and
generated a system reset
SD
Microcontroller internal fault generated a system
reset
SD
Microcontroller system reset line went active
WN
Ethernet communications lost with one or more
expected Main Controllers in an MPS
WN
Generator is out of service
WN
New Main Controller discovered on the MPS
Ethernet bus
WN
This generator is disabled via a PLC program
running on it
2
SD
I
T current threshold exceeded
SD
300% rated current exceeded for ten seconds
WN
Engine stopped running unexpectedly -
Generator shuts down and restarts
AL
Cranking voltage profile indicates starter did not
engage
SD
Bosch actuator position does not reflect
commanded position
Owner's Manual for Power Zone Pro Sync