Write down configuration of annunciator.
5.
Replace annunciator:
Replace the annunciator.
6.
Delete the old annunciator from the "Device Man-
ager" screen on each Display, and assign the new
annunciator a Friendly Name:
See
Figure
3-4. Select "Setup" (B).
7.
Select "Communications".
8.
Select "Device Manager".
9.
Select "Clear Devices". Repeat this step on ALL
10.
other Displays in the system including P&L Dis-
plays.
Go back to the "Device Manager" page on the Dis-
11.
play with the new annunciator.
Select the new annunciator entry in the "Ethernet
12.
Annunciators" list.
Select "Edit".
13.
Assign a Friendly Name for this annunciator and
14.
select "Save".
Configure the new annunciator:
See
Figure
3-4. Select "Setup" (B).
15.
Select "Modules".
16.
Select "Annunciator Setup".
17.
See
Figure
3-9. Under "Remote Annunciator", use
18.
the "Select a Name" dropdown to select the new
annunciator.
See
Figure
3-10. Under "Generator", use the
19.
"Select a Name" dropdown to select the generator.
Figure 3-10. Select Generator
Configure the annunciator settings and select
20.
"Save".
Verify the Controller is communicating with the
annunciator:
The "COMMS OK" LED on the annunciator should
21.
be lit solid green (no flashing) and the "SYSTEM
READY" LED should be flashing green.
Temporarily take the generator out of AUTO mode
22.
(only if it is safe to do so).
Verify the horn sounds and the "NOT IN AUTO"
23.