General Information
Voltage Regulation (Single or Three-Phase
Module Options)
•
Digital Control
•
Single-Phase or Three-Phase RMS Sensing with
Loss of Sensing Protection
•
Variable V/F Slope Settings and Adjustable Gains
•
Negative Power Protection
•
Soft Start Ramping
•
Paralleling Function
2
•
Fault Protection (I
PLC (Built-In Programmable Logic
Controller)
•
Configurable Through Software Tool
•
Customer Configurable for Non-Standard Options
•
Up to 8 PLC Programs Run Simultaneously or in
Sequence
Governor Module
•
Soft Start Ramping
•
Synchronizing Function (if equipped)
•
Fully Adjustable Gains (PID)
Connections
•
27 Digital Outputs Maximum (Open Drain, 35 V
1.7 A)
•
6 fast PWM capable outputs 1 High Current
•
26 Digital Inputs Maximum
•
6 fast PWM capable inputs
•
12 General Purpose Analog Inputs
•
4 Special Purpose Analog Inputs
•
4 Analog Outputs (0-10 V
•
1 E-Stop Relay Output
•
7 Current Sense Inputs
•
8 High Voltage Sense Inputs (Three (3) Phase +
Neutral)
•
2 Magnetic Pickup Inputs
•
1 Coolant Level Sensor Input
•
4 RJ-45 Controller Network Ethernet Ports
•
1 RJ-45 External Ethernet Port
•
3 CAN bus Channels
•
1 RS-485 Port
•
2 Switchable 12 V
NOTE: Actual I/O may vary due to configuration.
6
T Function and GFI)
)
Power Outputs
Qualification Testing
•
Life Test in Environmental Chamber
•
Temperature Rating
•
Humidity
•
Vibration Tested and Protected
Codes and Standards
•
UL 6200 Investigation of Controls for Stationary
Engine Driven Assemblies
•
UL 2200 Standard for Stationary Engine Generator
Assemblies
•
CSA STD C22.2 No. 14
•
EN 61010-1 Safety Requirements for Electrical
Equipment for Measurement, Control, and Labora-
tory Use
•
EN 61000-6-2 EMC Immunity for Industrial Envi-
ronments
•
EN 61000-6-4 EMC Emissions Standard for Indus-
trial Environments
•
NFPA 110 (configurable for Level 1 or 2) (with
additional optional remote annunciator)
•
NFPA 70 National Electrical Code for Safe Electri-
cal design, Installation, and Inspection
•
IEC801 Radiated Emissions, Susceptibility and
Surge Immunity
•
FCC and IC Canada (for Display only)
Protections
•
Sender Failure
•
Low Oil Pressure
•
Low Coolant Level
•
High/Low Coolant Temperature
•
High/Low Oil Temperature
•
Over/Under Speed
•
Over/Under Voltage
•
Over/Under Frequency
•
Over Current
•
Over Total kW
•
High/Low Battery Voltage
•
Battery Charge Current
•
Phase to Phase and Phase to Neutral Short
2
Circuits (I
T Algorithm and GFI)
Control Panel and Touch Screen
•
Auto/Manual/Off
•
Alarm Acknowledge Button
•
Audible Alarm
•
Emergency Stop
Owner's Manual for Power Zone Pro Sync