Voltage Regulation (Single Or Three-Phase Module Options); Plc (Built-In Programmable Logic Controller); Governor Module; Connections - Generac Power Systems Power Zone Pro Sync Owner's Manual

Table of Contents

Advertisement

General Information
Voltage Regulation (Single or Three-Phase
Module Options)
Digital Control
Single-Phase or Three-Phase RMS Sensing with
Loss of Sensing Protection
Variable V/F Slope Settings and Adjustable Gains
Negative Power Protection
Soft Start Ramping
Paralleling Function
2
Fault Protection (I
PLC (Built-In Programmable Logic
Controller)
Configurable Through Software Tool
Customer Configurable for Non-Standard Options
Up to 8 PLC Programs Run Simultaneously or in
Sequence

Governor Module

Soft Start Ramping
Synchronizing Function (if equipped)
Fully Adjustable Gains (PID)

Connections

27 Digital Outputs Maximum (Open Drain, 35 V
1.7 A)
6 fast PWM capable outputs 1 High Current
26 Digital Inputs Maximum
6 fast PWM capable inputs
12 General Purpose Analog Inputs
4 Special Purpose Analog Inputs
4 Analog Outputs (0-10 V
1 E-Stop Relay Output
7 Current Sense Inputs
8 High Voltage Sense Inputs (Three (3) Phase +
Neutral)
2 Magnetic Pickup Inputs
1 Coolant Level Sensor Input
4 RJ-45 Controller Network Ethernet Ports
1 RJ-45 External Ethernet Port
3 CAN bus Channels
1 RS-485 Port
2 Switchable 12 V
NOTE: Actual I/O may vary due to configuration.
6
T Function and GFI)
)
Power Outputs

Qualification Testing

Life Test in Environmental Chamber
Temperature Rating
Humidity
Vibration Tested and Protected

Codes and Standards

UL 6200 Investigation of Controls for Stationary
Engine Driven Assemblies
UL 2200 Standard for Stationary Engine Generator
Assemblies
CSA STD C22.2 No. 14
EN 61010-1 Safety Requirements for Electrical
Equipment for Measurement, Control, and Labora-
tory Use
EN 61000-6-2 EMC Immunity for Industrial Envi-
ronments
EN 61000-6-4 EMC Emissions Standard for Indus-
trial Environments
NFPA 110 (configurable for Level 1 or 2) (with
additional optional remote annunciator)
NFPA 70 National Electrical Code for Safe Electri-
cal design, Installation, and Inspection
IEC801 Radiated Emissions, Susceptibility and
Surge Immunity
FCC and IC Canada (for Display only)

Protections

Sender Failure
Low Oil Pressure
Low Coolant Level
High/Low Coolant Temperature
High/Low Oil Temperature
Over/Under Speed
Over/Under Voltage
Over/Under Frequency
Over Current
Over Total kW
High/Low Battery Voltage
Battery Charge Current
Phase to Phase and Phase to Neutral Short
2
Circuits (I
T Algorithm and GFI)

Control Panel and Touch Screen

Auto/Manual/Off
Alarm Acknowledge Button
Audible Alarm
Emergency Stop
Owner's Manual for Power Zone Pro Sync

Advertisement

Table of Contents
loading

Table of Contents