GEM 4242 Operating Instructions Manual page 38

Combi switchbox with integrated pilot valve
Table of Contents

Advertisement

15 Specific data – AS-Interface
Port
Index
"Access
[Hex]
Rights"
1
0x67A1 RW
1
0x67A2 RW
1
0x67A3 RW
1
0x67A4 RW
1
0x67A5 RW
1
0x67A6 RW
1
0x67A7 RW
* These parameters are not reset to default settings with the "Restore Factory Settings" AS-I system command, but instead re-
tain their set values
GEMÜ 4242
Parameter
"Length
Alarm threshold for
2 byte
min. internal temperat-
ure of housing
Alarm threshold for
2 byte
max. internal temper-
ature of housing
Alarm threshold for
2 byte
min. humidity of hous-
ing
Alarm threshold for
2 byte
max. humidity of hous-
ing
Alarm threshold for
2 byte
high oscillations
Alarm threshold for
2 byte
min. internal pressure
of housing
Alarm threshold for
2 byte
max. internal pressure
of housing
"Data
"Default set-
"
type"
ting"
int:16
-5 °C
int:16
75 °C
int:16
0.0%
int:16
100.0 %
int:16
0.0%
int:16
500mbar
int:16
1230 mbar
38 / 51
"Adjustment
"Description"
facility"
5
Safe/On
If the signal is not act-
ive, the position
defined in the "Error-
Action" (0x004F) para-
meter is approached.
If the signal is active,
normal operation is
carried out in accord-
ance with external sig-
nals.
-40 to 100 °C Defines the threshold
below which an alarm
signal will be gener-
ated to indicate the in-
ternal temperature of
the housing is too low
-40 to 100 °C Defines the threshold
above which an alarm
signal will be gener-
ated to indicate the in-
ternal temperature of
the housing is too high
0.0 to
Defines the threshold
100.0%
below which an alarm
signal will be gener-
ated to indicate the
humidity inside the
housing is too low
0.0 to
Defines the threshold
100.0%
above which an alarm
signal will be gener-
ated to indicate the
humidity inside the
housing is too high
0.0 to
Defines the threshold
100.0%
above which an alarm
signal will be gener-
ated to indicate the
oscillations are too
high
260–1260
Defines the threshold
mbar
below which an alarm
signal will be gener-
ated to indicate the in-
ternal pressure in the
housing is too low
260–1260
Defines the threshold
mbar
above which an alarm
signal will be gener-
ated to indicate the in-
ternal pressure in the
housing is too high
www.gemu-group.com