11.2 Potential equalization – Special function X
The potential equalization can be established using the following methods:
- Pre-assembled earthing kit for the on-site wiring of the earth via a stranded wire, yellow/green H07 V-K 4.0
- Conductive connection via the mechanically coupled valve fitting to the system earth
Connecting the potential equalization device
1. Use a screw M4x6 to attach the potential equalization device to the electrical position indicator.
ð Potential equalization for metal housings in potentially explosive areas: Minimum 4 mm².
2. Secure the connection against working itself loose.
The potential equalization connection's maximum permissible resistance limit value is defined as R ≤ 100 Ω. During the plant-
specific maintenance cycle, the potential equalization connection must be checked to ensure that it has been connected cor-
rectly and that the maximum resistance limit value has not been exceeded.
www.gemu-group.com
Signal name
21 / 51