GEM 4242 Operating Instructions Manual page 27

Combi switchbox with integrated pilot valve
Table of Contents

Advertisement

No.
Parameter
P27
Digital output 6 function
P28
Digital output 7 function
P29
Digital output 8 function
S04
Absolute travel sensor posi-
tion CLOSED/OPEN
S15
Warning threshold for valve
activations user counter
S13
Valve activations total
counter
P08
Error time
Acceleration in X axis
Acceleration in Y axis
Acceleration in Z axis
Frontally inclined installation
position
Current consumption
Supply voltage
P33
Alarm threshold for min. in-
ternal temperature of housing
P34
Alarm threshold for max. in-
ternal temperature of housing
P35
Alarm threshold for min. hu-
midity of housing
P36
Alarm threshold for max. hu-
midity of housing
Humidity of housing
www.gemu-group.com
Description
Defines the function of digital
output 6
Defines the function of digital
output 7
Defines the function of digital
output 8
Displays the valve absolute
position for the end positions
Defines the warning threshold
for the user counter for valve
activations
Displays the total number of
counted valve activations
Defines the debounce time in
the event of error detection
Indicates the measured accel-
eration of the X axis
Indicates the measured accel-
eration of the Y axis
Indicates the measured accel-
eration of the Z axis
Indicates the frontally inclined
installation position detected
Indicates the measured cur-
rent consumption
Indicates the measured supply
voltage
Defines the threshold below
which an alarm signal will be
generated to indicate the in-
ternal temperature of the
housing is too low
Defines the threshold above
which an alarm signal will be
generated to indicate the in-
ternal temperature of the
housing is too high
Defines the threshold below
which an alarm signal will be
generated to indicate the hu-
midity inside the housing is
too low
Defines the threshold above
which an alarm signal will be
generated to indicate the hu-
midity inside the housing is
too high
Indicates the measured relat-
ive humidity inside the hous-
ing
27 / 51
Value range
Deactivated
OPEN feedback
CLOSED feedback
Error output
Warning output
Operating mode feedback
Deactivated
OPEN feedback
CLOSED feedback
Error output
Warning output
Operating mode feedback
Deactivated
OPEN feedback
CLOSED feedback
Error output
Warning output
Operating mode feedback
 0 ... 100 %
0 ... 2147483647 Cycles
 0 ... 2147483647 Cycles
 1 ... 1000  s
-32768 ... 32768 m/s2
-32768 ... 32768 m/s2
-32768 ... 32768 m/s2
-180 ... 180 °
0 ... 375 mA
0 ... 3600 mV
-40 ... 100 °C
-40 ... 100 °C
0 ... 100 %
0 ... 100 %
0 ... 100 %
14 App parameter list
Default setting
Deactivated
Deactivated
Deactivated
 0
5000000
0
0.1
-5.0
75.0
50.0
90.0