6 TROUBLESHOOTING
Error number
Error message
Cause
Solution
H2370 *
Error message
Cause
Solution
Error message
Cause
Solution
Error message
L3880
Cause
Solution
Error message
Cause
Solution
Error message
H8250
Cause
Solution
Error message
Cause
H8252
Solution
Error message
Cause
H8253
Solution
Error message
Cause
H8254
Solution
Error message
Cause
H8257
Solution
6-86 Error List for the Safety Monitoring Functions
Error causes and solutions
SF (Process error)
The Safety Function is not normally executed.
Reset the error by power-cycling the robot. If the same error recurs, contact the
manufacturer.
SF (Process Counter error)
The Safety Function of servo CPU is not normally executed.
Reset the error by power-cycling the robot. If the same error recurs, contact the
manufacturer.
Invalid SCNI number in M_SCNI
Invalid SCNI number is input in M_SCNI.
Enter any value of 1 to 8.
Invalid LOGIC no. in M_SCNILogic
Invalid LOGIC number is input in M_SCNILogic.
Enter any value of 1 to 3.
Invalid SCNO number in M_SCNO
Invalid SCNO number is input in M_SCNO.
Enter any value of 1 to 4.
Safety comm. Received error info
Error information was received from the master station with which the safety
communication function (CC-Link IE TSN) is communicating.
Check the master station error.
Safety comm. timeout
A timeout error occurred in the safety communication function (CC-Link IE TSN).
・ Check that the parameter "safety refresh monitoring time" set on the master
station is an appropriate value.
・ Check if measures against noise in the transmission path are taken and wiring
and devices have no problems.
・ Check that no online operation is being performed from a peripheral such as the
engineering tool, or no program or parameter is being written to the master station.
・ If the same error occurs again, the possible cause is a hardware failure. Contact
the manufacturer.
Safety comm. timeout
A timeout error (unacceptable delay) has occurred in the safety communication
function (CC-Link IE TSN).
・ Check that the parameter "safety refresh monitoring time" set on the master
station is an appropriate value.
・ Check that the parameter "transmission interval monitoring time" set on the
robot controller is an appropriate value.
・ Check if measures against noise in the transmission path are taken and wiring
and devices have no problems.
・ Check that no online operation is being performed from a peripheral such as the
engineering tool, or no program or parameter is being written to the master station.
・ If the same error occurs again, the possible cause is a hardware failure. Contact
the manufacturer.
Safety comm. timeout
A transmission interval error (communication destination) of the safety
communication function (CC-Link IE TSN) has occurred.
・ Check that the parameter "transmission interval monitoring time" set on the
master station (communication destination) is an appropriate value.
・ Check if measures against noise in the transmission path are taken and wiring
and devices have no problems.
・ Check that no online operation is being performed from a peripheral such as the
engineering tool, or no program or parameter is being written to the master station.
・ If the same error occurs again, the possible cause is a hardware failure. Contact
the manufacturer.
Safety comm. data error
A data error has occurred in the safety communication function (CC-Link IE TSN).
If the same error occurs again, the possible cause is a hardware failure. Contact
the manufacturer.