Safety Refresh Monitoring Time - Mitsubishi Electric CR800-R Instruction Manual

Industrial robot, safety communication function
Hide thumbs Also See for CR800-R:
Table of Contents

Advertisement

8 SYSTEM APPLICATION EXAMPLES

Safety refresh monitoring time

8.2.11
Check the conditions of the safety refresh monitoring time (RM). The following shows calculation examples.
Item
Description
TMact
Transmission interval monitoring time on the active
side
(Transmission interval monitoring time to be set on
the safety programmable controller)
TMpas
Transmission interval monitoring time on the
passive side
(Transmission interval monitoring time to be set on
the robot controller)
LS
Communication cycle intervals
SCact
Safety cycle time on the active side
(Safety cycle time of the safety CPU module:
SCcpu)
SCpas
Safety cycle time on the passive side
(Safety cycle time of the robot controller: SCrc)
a
TMact - b
b
A smallest multiple of SCact which is greater than
TMact /2
c
TMpas - d
d
A smallest multiple of SCpas which is greater than
TMpas /2
The safety refresh monitoring time (RM) must satisfy all of the following conditions. Set a value equal to or higher
than 28.0 [ms].
(1) RM ≥ TMact + (TMpas /2) + (LS × 2) - a + (SCpas /2)
= 16.30 + (21.40 /2) + (1.00 × 2) - 7.30 + (7.11 /2)
= 25.26
(2) RM ≥ (TMact /2) + TMpas + (LS × 2) - c + (SCpas /2)
= (16.30 /2) + 21.40 + (1.00 × 2) - 7.18 + (7.11 /2)
= 27.93
(3) RM > TMact
= 16.30
(4) RM > TMpas
= 21.40
8-132 Application Example 2
Table 8-15 Parameters
Value
Remarks
16.30[ms]
Setting value
21.40[ms]
Setting value
1.00[ms]
Setting value
3.00[ms]
Setting value
7.11[ms]
-
7.30
Calculated
value
9.00
Calculated
value
7.18
Calculated
value
14.22
Calculated
value

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cr860-rMelfa bfp-a3772-d

Table of Contents