Table 22. Configuration settings of the motor control board (for reference only) (continued)
User
Description on
Interface
Unit Label
Name
Ehpt
Protect Funct
rpdf
Rmp dft (auto rst)
soft
Soft Rev
Fan Speed Response Verification
1. After performing controller specific commissioning,
observe the display on the motor control board with the
power on, to the unit. The motor control board display
should display a looping status indicator as follows:
Mtr1
0
Mtr2
ff
Fst2
Off
EhEn
Notes:
EhEn
The
indicator is unit-specific and may indicate "Off"
at this point; refer to thermistor function for more
information.
A representative fan speed of "1080" rpm are shown in the
example below. Each unit is factory-configured differently
and will have different settings for different fan speeds.
2. While the unit remains on, exercise the fan controls on the
unit, either directly or indirectly through request for unit
heat/cool. Observe the fan spinning, and then observe the
fan display on the motor control board. It should display a
looping status indicator as follows:
For a size 200, 300, 400, 600, or 800 unit (using typical unit
operating fan speeds):
UV-SVX005G-EN
Typical User
Interface Value
This his function protects settings on the board that
affect the safety of the electric heat system, and limit
FLA
the maximum current the motor will draw under any
operating condition.
This function shortens the ramps for faster unit
off
commissioning and auto-resets to off after
approximately 15 minutes of power-on operation.
vx.xx
Displays the software version.
0
FSt1
On
Description
Mtr1
1080
On
Off
EhEn
For a size 1000 or 1200 unit (using typical unit operating
fan speeds):
Mtr1
1080
O
1
On
on
EhEn
EhEn
Note: The
"Off" at this point; refer to thermistor function for more
information.
3. OPTIONAL:
While the fan is running, if practical, change the fan speeds
and observe the display temporarily indicate:
Exercise all fan speeds to ensure positive unit response
and to validate any field wiring.
ECM Overview and Setup
Do NOT change this setting. This setting locks out the
following parameters from being changed, for safe
operation of the unit.
E1M1
E2M1
E1M2
E2M2
MOD1
MOD2
sI91
SI92
M1HI
M1LO
M2HI
M2LO
FPRV
A12M
A12B
AIPU
To aid in commissioning of the unit, for approximately
10–15 minutes, the ramps will be shortened to quickly
observe proper unit behavior and response to speeds.
Module should be received with most recent version.
Mtr2
0
Fst2
On
Mtr2
1080
Fst2
On
indicator is unit-specific and may indicate
FSt1
FSt
ramp
69