Table 51. Tracer® ZN520 test sequence
Step
1(a)
1.
Off
(b)
2.
Fan high
(c)
3.
4.
Fan low
5.
Main open
6.
Main close, EH1 on
7.
Aux. open
8.
Aux. close, damper open
9.
Damper close
10. Generic/baseboard heat
energized
(e)
11. Exit
(a) Upon entering manual output test mode, the controller turns off all fan and electric heat outputs and drives.
(b) At the beginning of
Step
2, the controller attempts to clear all diagnostics.
(c) The low fan speed output energizes at
(d) If the unit is configured for a 1- or 2-speed fan, and BOP2 is configured for an exhaust fan, the exhaust fan output energizes on
medium speed.
(e) After
Step
10, the test sequence performs an exit. This initiates a reset and attempts to return the controller to normal operation.
Translating Multiple Diagnostics
The controller senses and records each diagnostic
independently of other diagnostics. It is possible to have
multiple diagnostics present simultaneously. The diagnostics
are reported in the order they occur.
Possible diagnostics include:
Low coil temperature detection
Condensate overflow
Low air flow—fan status
Discharge air temp limit
Space temperature failure
Entering water temp failure
Discharge air temp failure
Outdoor air temp failure
1
Local setpoint failure
1
Local fan mode failure
1
CO
sensor failure
2
1
Generic AIP failure
1
Humidity input failure
Defrosting compressor lockout
2
Maintenance required
Invalid Unit Configuration
Generic temperature failure
Discharge air low limit
Resetting Diagnostics
There are seven ways to reset unit diagnostics:
Automatically by the controller
By initiating a manual output test at the controller (Tracer®
ZN520 only)
1
Non-latching diagnostics automatically reset when the input is present and valid.
2
Does not apply to the UC400-B/Symbio™ 400-Bcontroller.
UV-SVX005G-EN
Fan
Main Valve
J1-1
J1-2
J1-3
Off
Off
Off
High
Off
Off
Off
Off
Off
Off
Low
High
Off
Off
High
Off
Off
High
(d)
Exh
Off
EH1 on
High
Off
Off
High
Off
Off
High
Off
Off
Exit
Step
3. If the unit is configured for a 1-speed fan, the fan remains on high speed at
1
1
1
1
2
2
Diagnostics and Troubleshooting
Electric Heat or Aux.
Fresh Air
Valve
Damper
J1-5
J1-6
J1-9
On
Off
Off
EH: off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
On
On
Off
Off
On
Off
Off
Off
EH1 off
Off
Off
Off
Off
Off
Off
By cycling power to the controller
By using a building automation system
By using the Rover service tool
By using any other communicating device able to access
the controller's diagnostic reset input (Tracer® ZN520
only)
By cycling the fan switch from off to any speed setting
(Tracer® ZN520 only)
Automatic Reset by the Controller
The controller includes an automatic diagnostic reset function
which attempts to automatically restore the unit when a low
temperature diagnostic occurs.
Note: The controller implements the automatic diagnostic
reset function only once every 24 hours. For the
controller to increment the 24-hour timer, you must
maintain power to the controller. Cycling power resets
all timers and counters.
After the controller detects the first low temperature diagnostic,
the unit waits 30 minutes before invoking the automatic
diagnostic reset function. The automatic diagnostic reset
function clears the special diagnostic and attempts to restore
the controller to normal operation. The controller resumes
normal operation until another diagnostic occurs.
Note: The automatic diagnostic reset function does not
operate during the manual output test sequence.
If a special diagnostic occurs within 24 hours after an
automatic diagnostic reset, the controller must be manually
reset. Other possible methods of resetting diagnostics are
described in the sections that follow.
Generic/Baseboard Heat
J1-10
J1-11
J1-12
aux: on
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
Off
EH2 on
Off
Off
On
Off
Off
Off
Step
3.
Step
7. The exhaust fan output is shared with
TB4-1
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
105