Diagnostics and Troubleshooting
Testing Battery Status
Initiate a battery status test as follows:
On the WZS, push the Test button on the sensor (see
location on
Figure 87, p.
Table 42. Battery status indicated by LED5 on the wireless zone sensors
User action
LED state
Solid green for 5 seconds
Press Test
Solid red for 5 seconds
button
No light
Blinking red: 1-blink pattern
None
repeats every 15 minutes.
(a) Blink pattern is On for 1/4 s, Off for 3/4 s, with 2 s Off between repetitions.
Table 43. Battery status shown on the wireless display sensor
Battery test
User action
symbol
Press Test button
24 V Power Status Indicator
LED5 on the receiver of all models (see
and stays constantly On when 24 V power is normal.
Check Signal Strength on a Site
Use the wireless sensor system to check the signal strength on
a site.
1. Power up a receiver with a 24 V transformer (user
supplied).
2. Associate the sensor to a receiver of the same model
intended for the job.
3. Place the receiver at the desired location.
4. Place or hold the sensor at the desired location.
5. Press the Test button (S5) on the sensor and observe the
signal strength as indicated by LED1, LED2, and LED3 on
model WZS (see
Figure 87, p.
model WDS (see
Figure 88, p.
For more information on interpreting the LEDs and the display
symbols that indicate signal strength, see
Strength," p.
99.
Replacing Sensor Batteries
Sensor battery type, length of life, and installation are
addressed in this section.
100
97). LED5 on the sensor
(a)
repeated 5 times. Cycle
Battery test
Indicates...
symbol
Full battery power.
Figure 86, p.
97) lights
97), and on the display on
97).
"Testing Signal
responds by indicating the level of battery strength, as
shown in
Table 42, p.
On the WDS, push the Test button on the sensor (see
location on
Figure 88, p.
symbol appears on the display. The symbol shown
indicates battery life expectancy (see
Indicates...
Battery is adequate for proper operation.
25% battery life left. Batteries should be replaced.
Batteries life expired or not installed properly, or sensor is defective.
Approximately 14 days of operation remain before the battery is too weak to power the
sensor.
Battery test
Indicates...
symbol
50percent battery
life left.
Battery Type
Equipment Damage!
The batteries are manufactured in a ready-to-use state.
They are not designed for recharging. Recharging can
cause battery leakage or, in some cases, can cause the
safety release vent to open.
Equipment Damage!
Do not attempt to hook up the sensor to a power
supply. Equipment damage may result.
Use two non-rechargeable 1.5 V lithium AA batteries in the
sensor. To maintain UL rating, use only UL-listed lithium
batteries. The sensor ships with Energizer
already installed. Replacement batteries are available at Trane
Service Parts Centers (p/n X13770035010) or other local
suppliers.
Battery Life
Battery life is five years under normal conditions. If the sensor
is not used for an extended period of time, do one of the
following:
Set the sensor address to 000 to place the sensor into a
low-power hibernation mode.
Remove the batteries
100.
97). In response, a battery test
Table 43, p.
Indicates...
25 percent battery life left. Replace batteries.
Flashing symbol indicates that approximately 14 days
of operation remain before the battery is too weak to
power the sensor.
NOTICE
NOTICE
®
L91 batteries
UV-SVX005G-EN
100).