ECM Overview and Setup
Table 20. Button actuation levels
Button
Short Press in
Status Display
Short Press in Configuration Display
Long Press/Hold
in Status Display
Long Press/Hold
in Configuration Display
Button
Short Press in
Status Display
Short Press in Configuration Display
Long Press/Hold
in Status Display
Long Press/Hold
in Configuration Display
Button
Short Press in
Status Display
Short Press in Configuration Display
Long Press/Hold
in Status Display
Long Press/Hold
in Configuration Display
Configuration Examples
Example 1:
View the value of parameters without saving.
Verify the low speed value for motor 1 is set to 800 rpm.
Figure 70. Verify low speed value
Example 2:
Change the value of Low Speed to 820 rpm:
Continue from the previous example as shown below, using a
long press to "save" the new desired value.
If the display has timed out and returned to the status loop,
repeat Example 1 to arrive back at this example's starting
point.
Example 3:
Double-check the value of 820 rpm has been
saved.
If the display has timed out and returned to the status loop,
60
Duration
<1 sec
>3 sec
>3 sec
Duration
<1 sec
<1 sec
>3 sec
>3 sec
Duration
<1 sec
<1 sec
>3 sec
Menu/Set
Action
None
Toggles between parameter name and value without saving (abandons value if
changed).
Enters the configuration menu
If on a parameter name, toggles to the value. If on a parameter value, saves the
value settings and returns to the parameter name as confirmation.
Decrement
Action
None
Scrolls through parameter names, or decreases value of parameter.
n/a
Faster scroll through parameter name, or faster decrease of values of
parameters.
Increment
Action
None
Scrolls through parameter names, or increases value of parameter.
n/a
Faster scroll through parameter name, or faster increase of values of
parameters.
Sart with the motor control board scrolling status display and
proceed as follows:
Figure 71. Change value of low speed value
repeat Example 1 and Example 2 to arrive back at this
example's starting point.