Component Data - Trane VUV Installation, Operation And Maintenance Manual

Vertical classroom unit ventilator
Table of Contents

Advertisement

Dimensions and Weights

Component Data

Table 1.
Vertical unit ventilator general data
Description
Unit length without end covers (in.)
Unit depth - standard (in.)
Unit depth - with false back (in.)
Unit height - standard (in.)
Shipping weight (lb)
Nominal filter size (in.) and quantity
Dynamic air filter nominal size (in.) and quantity
Drain connection size (in.)
Fan type / quantity
Motor data - quantity/horsepower
Coil volume (gal)
Coil type A
Coil type B
Coil type C
Coil type D
Coil type E
Coil type F
Coil type G
Coil type H
Table 2.
Control methodology
Method
CSTI
ZN520
Symbio™ 400-B
UC400-B/
Thermostat
(a) With a field-supplied 2-10 Vdc controller.
Table 3.
Control sequences
Sequence
(a)
DX operation
Electric heat
operation(a)
(a) Fan speed during sequence operation.
12
0750
69.00
16 5/8
21 1/4
30.00
320
14 x 20 x 1 (2)
7 x 42 x 1 (1)
7/8-in. I.D.
FC / 2
1 - 1/4
0.18
0.31
0.31
0.44
0.44
0.61
0.61
0.40
Fan Speeds
(a)
3 or infinite
3
Infinite
3
Fan Speeds
1
1
Unit size
1000
1250
81.00
93.00
16 5/8
16 5/8
21 1/4
21 1/4
30.00
30.00
405
450
14 x 24 x 1 (1)
14 x 20 x 1 (2)
14 x 30 x 1 (1)
14 x 24 x 1 (1)
7 x 54 x 1 (1)
7 x 66 x 1 (1)
7/8-in. I.D.
7/8-in. I.D.
FC / 2
FC / 4
1 - 1/4
2 - 1/4
0.23
0.28
0.41
0.51
0.41
0.51
0.57
0.70
0.57
0.70
0.81
1.01
0.81
1.01
0.59
0.74
1500
105.00
16 5/8
21 1/4
30.00
470
14 x 24 x 1 (2)
14 x 30 x 1 (1)
7 x 78 x 1 (1)
7/8-in. I.D.
FC / 4
2 - 1/4
0.33
0.61
0.61
0.93
0.93
1.21
1.21
0.84
UV-SVX005G-EN