LOCATION 9 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE N° 2 (2 segments, numerical data)
Segment 1, dial attempts: segment 1 of location 9 is used to enter the number of dial
attempts (1 to 15 attempts) that the communicator will make to phone N°2 before it ends the
notification process. Factory default is "0", and the communicator will make the same number
of attempts as those programmed in location 3.
There will be a waiting time of 12 seconds between the first two dial attempts, and a
waiting time of 60 seconds between each subsequent dial attempt (regardless of the
number dialled).
Segment 2, phone N° 2 backup control: Programming a "0" in segment 2 of this location will
cause the NX-8 to make the designated number of attempts to phone N°1 before setting the
"fail to communicate" condition and stop reporting. Programming a "1" in this segment will
cause the NX-8 to stop trying to communicate after the designated number of attempts have
been made to phone N°2. If a "2" is programmed in this segment, it will cause the NX-8 to
make the dial attempts in increments of two. The first two attempts will be made to phone
N°2, the next two attempts to phone N°1, then repeating until the total number of attempts
designated in segment 1 is completed.

Reporting events to phone number 2

Phone N°2 can be used to back up phone N°1, or as a second receiver to multi-report or split-
report events. Phone N°2 has two programming locations that are used to select the events
that are reported to this phone number. Location 10 is used to select the events which are
reported to phone N°2, and location 11 is used to select which partitions are reported to
phone N°2. If you do not want dual or split reporting, location 10 and location 11 should be left
at the factory default of "0". If you want multi-reporting or split reporting, and the split is based
on the event type (such as alarm, open close etc.), location 10 should be used to select only
those events that should be reported to phone N°2, and location 11 should be left at the
factory default of "0". If you want dual or split reporting, and the split is based on partition,
then location 10 should be programmed as "0", and location 11 should be used to select those
partitions that are to be reported to phone N°2. If no events are to be reported to phone N°2,
both locations should be at "0".
LOCATION 10 - EVENTS REPORTED TO PHONE N° 2 (2 segments of feature selection data)
Segment 1
NX-8-EUR Installation manual
1 =
Alarms
2 =
Opening and closings
3 =
Zone bypass and bypass restores
4 =
Zone trouble and trouble restores
5 =
Power fail (AC failure), low battery, power restore (AC restore) , and low
battery restore
6 =
Bell cut, bell cut restore, telephone line restore
7 =
Test reports
8 =
Start and end programming, download complete and log full
Page 39