Muting and override
38
DIRECTIONS
Note • d is the resulting distance between the activation points of Muting A and
Muting B. It needs to be checked in regards to the speed of the material
transport.
Timing requirements and limitations:
• Either Muting A or Muting B can be used to initiate the muting function.
• There is no maximum time limit after Muting A is activated.
• There is no maximum time limit after Muting B is activated.
• Muting A and Muting B cannot be activated at the same time. A minimum
time difference equal to the response time of the sensor is mandatory.
• Maximum muting time is 1700 sec. After this time, muting function is
stopped even if the Muting inputs are still active.
• The F3S-TGR-CL allows that Muting A or Muting B drop for a maximum
time of 200 ms without stopping the muting function. A time longer than
200 ms is detected as a muting stop.
SLC
Interrupted
OSSD
Muting
Input A
Muting
Input B
Muting
Status
RT
< TM < ∞s
Mut sen.
A
ALLOWED
GOODS
d
DANGEROUS
AREA
Free
ON
OFF
ON
OFF
ON
OFF
Active
OFF
RT
Section 11-1
Mut sen.
B
F3S-TGR-CL
SAFE
AREA
FENCE
< 0,2s
> 0,2s