Minimum clearances
To enable operation and maintenance and to ensure proper ventilation of the charging
station, you need to maintain the following minimum clearances:
Figure 5-1  Minimum clearances of SICHARGE D, top view
We recommend that you set up the charging station as free-standing as possible. If you
position two SICHARGE D next to each other, then maintain twice the minimum distances
between the two devices. The cooling concept is maintained in this way. Note the swivel
range of the door.
You need a minimum distance from the top of the charging station to the ceiling for
maintenance at the planned location. Depending on the conditions on site and the procedure
for setting up the charging station, the minimum clearance required could be greater for
assembly reasons.
Table 5-1  Minimum distance to the ceiling
Charging station with cable management sys­
tem (CMS)
No
Yes
SICHARGE D
Operating Instructions, 11/2023, A5E50556539-AG
Installation and mounting
5.2 Installation location
Minimum distance to the ceiling
200 mm
250 mm
73