AYK550-UH User's Manual
Group 12: Constant Speeds
This group defines a set of constant speeds. In general:
• You can program up to 7 constant speeds, ranging from 0...500 Hz or 0...30000
rpm.
• Values must be positive (No negative speed values for constant speeds).
• Constant speed selections are ignored if:
– the torque control is active, or
– the process PID reference is followed, or
– the drive is in local control mode, or
– PFA (Pump and Fan Alternation) is active
Note! Parameter 1208
may be activated if the control signal is lost. Refer to parameter 3001
and parameter 3002
Code
Description
1201
CONST SPEED SEL
Defines the digital inputs used to select Constant Speeds. See general comments in the introduction.
0 =
– Disables the constant speed function.
NOT SEL
1 =
1 – Selects Constant Speed 1 with digital input
DI
• Digital input activated = Constant Speed 1 activated.
2...6 =
2...
6 – Selects Constant Speed 1 with digital input
DI
DI
7 =
1,2 – Selects one of three Constant Speeds (1...3) using
DI
• Uses two digital inputs, as defined below (0 =
1
2
DI
DI
0
0
No constant speed
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
• Can be set up as a so-called fault speed, which is activated if the control signal is lost. Refer to parameter 3001
<
function and parameter 3002
AI
MIN
8 =
2,3 – Selects one of three Constant Speeds (1...3) using
DI
• See above (
1,2) for code.
DI
9 =
3,4 – Selects one of three Constant Speeds (1...3) using
DI
• See above (
1,2) for code.
DI
10 =
4,5 – Selects one of three Constant Speeds (1...3) using
DI
• See above (
1,2) for code.
DI
11 =
5,6 – Selects one of three Constant Speeds (1...3) using
DI
• See above (
1,2) for code.
DI
CONST SPEED
PANEL COMM ERROR
Group 12: Constant Speeds
Range
-14 ...19
DI
de-activated, 1 =
DI
Function
PANEL COMM ERR
7 acts also as a so-called fault speed which
. For HVAC, do not set speeds over 60 Hz.
Resolution
1
1.
2...
6. See above.
DI
DI
1 and
2.
DI
DI
activated):
DI
.
2 and
3.
DI
DI
3 and
4.
DI
DI
4 and
5.
DI
DI
5 and
6.
DI
DI
64
<
AI
MI FUNCTION
Default
S
3
Start-Up

Advertisement

Table of Contents
loading

Table of Contents