York AYK 550 User Manual page 226

Air modulators
Hide thumbs Also See for AYK 550:
Table of Contents

Advertisement

222
Ratings, 208...240 Volt Drives
Abbreviated column headers are described in "Symbols" on page 222.
AYK550-UH-see below
Three-phase supply voltage, 208...240 V
-04A6-2
-06A6-2
-07A5-2
-012A-2
-017A-2
-024A-2
-031A-2
-046A-2
-059A-2
-075A-2
-088A-2
-114A-2
-143A-2
-178A-2
-221A-2
-248A-2
Symbols
Typical ratings:
Normal use (10% overload capability)
I
2N
P
N
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1: The ratings apply in ambient temperature of 40 °C (104 °F).
Technical Data
Valid up to 40°
Type Code
I
2N
A
4.6
6.6
7.5
11.8
16.7
24.2
30.8
46.2
59.4
74.8
88.0
114
143
178
221
248
continuous rms current. 10% overload is allowed for one minute in ten minutes.
I
1,1x
N
I
N
1 min.
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The Horsepower ratings apply to most 4-pole NEMA motors.
C (104 °F)
Frame Size
P
P
N
N
kW
HP
1.1
1.0
R1
1.5
1.5
R1
2.2
2.0
R1
3.0
3.0
R1
4.0
5.0
R1
5.5
7.5
R2
7.5
10.0
R2
11.0
15.0
R3
15.0
20.0
R3
18.5
25.0
R4
22.0
30.0
R4
30.0
40.0
R4
37.0
50.0
R6
45.0
60.0
R6
55.0
75.0
R6
75.0
100
R6
9 min.
AYK550-UH User's Manual
1 min.