HVAC Default
This macro provides the factory default parameter settings for the AYK550-UH.
Factory defaults can be restored at any time by setting parameter 9902 to 1. The
diagram below shows typical wiring using this macro. When using direct speed
reference in AUTO mode or process PID, see "General Considerations" on page 30.
None (Default macro)
Note! YORK Drives are pre-configured using the "HVAC" default macro. Changing
user macros may require changes to factory control wiring.
Start-Up
X1
1
SCR
Signal cable shield (screen)
2
AI1
External reference 0(2)...10 V or 0(4)...20 mA
+
3
AGND
Analog input circuit common
4
10V
Reference voltage 10 VDC
5
AI2
PID feedback: 0(2)...10 V or 0(4)...20 mA
+
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0(4)...20 mA
mA
8
AO2
Output current: 0(4)...20 mA
mA
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24V
Common for DI return signals.
11 GND
Digital input common for all
12 DCOM1
Start/Stop: Activate to start drive
13 DI1
Not configured
14 DI2
Constant (Preset) speed 1 (P 1202)
15 DI3
Safety interlock: Deactivate to stop drive (P 1608)
16 DI4
Not configured
17 DI5
Not configured
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
Parameters Changed Relative to HVAC Default
Parameter
Relay output 1 (P 1401)
Default operation: Ready =>19 connected to 21
Relay output 2 (P 1402)
Default operation: Running =>22 connected to 24
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
(Fault => 25 connected to 26)
Value
AYK550 User's Manual
J1
Jumper Settings
AI1: 0(2)
AI2: 0(4)
Parameter
...
10 V
...
20 mA
Value