York AYK 550 User Manual page 229

Air modulators
Hide thumbs Also See for AYK 550:
Table of Contents

Advertisement

AYK550-UH User's Manual
380...480 Volt Drives
AYK550-UH-
see below
-03A3-4
-04A1-4
-06A9-4
-08A8-4
-012A-4
-015A-4
-023A-4
-031A-4
-038A-4
-044A-4
-059A-4
-072A-4
-077A-4
-096A-4
-124A-4
-157A-4
-180A-4
208...240 Volt Drives
AYK550-UH-
see below
-04A6-2
-06A6-2
-07A5-2
-012A-2
-017A-2
-024A-2
-031A-2
-046A-2
-059A-2
-075A-2
-088A-2
-114A-2
-143A-2
-178A-2
-221A-2
-248A-2
Input Current (A)
IEC269 gG (A)
3.3
10
4.1
6.9
8.8
11.9
16
15.4
23
25
31
35
38
50
44
59
63
72
80
77
96
125
124
160
157
200
180
250
Input Current
A
IEC269 gG (A)
4.6
10
6.6
7.5
11.8
16
16.7
25
24.2
30.8
40
46.2
63
59.4
74.8
80
88.0
100
114
125
143
200
178
250
221
315
248
Input Fuses
UL Class T (A)
Bussmann Type
10
JJS-10
15
JJS-15
20
JJS-20
30
JJS-30
40
JJS-40
50
JJS-50
60
JJS-60
80
JJS-80
90
JJS-90
100
JJS-100
125
JJS-125
175
JJS-175
200
JJS-200
250
JJS-250
Input Fuses
UL Class T (A)
Bussmann Type
10
JJS-10
15
JJS-15
25
JJS-25
30
JJS-30
40
JJS-40
60
JJS-60
80
JJS-80
100
JJS-100
110
JJS-110
150
JJS-150
200
JJS-200
250
JJS-250
300
JJS-300
350
JJS-350