York AYK 550 User Manual page 110

Air modulators
Hide thumbs Also See for AYK 550:
Table of Contents

Advertisement

AYK550-UH User's Manual
Code Description
5 =
(0) – Sensor configuration uses a thermistor.
THERMISTOR
• Motor thermal protection is activated through a digital input. Connect either a PTC sensor or a normally closed
thermistor relay to a digital input. The drive reads the digital input states as shown in the above table.
• When the digital input is '0' the motor is overheated.
• See the figures in the introduction to this Group.
6 =
(1) – Sensor configuration uses a thermistor.
THERMISTOR
• Motor thermal protection is activated through a digital input. Connect a normally open thermistor relay to a digital
input. The drive reads the digital input states as shown in the above table.
• When the digital input is '1' the motor is overheated.
See the figures in the introduction to this Group.
3502 INPUT SELECTION
Defines the input used for the temperature sensor.
1 =
1 – PT100 and PTC.
AI
2 =
2 – PT100 and PTC.
AI
3...8 =
1...
6 – Thermistor
DI
DI
3503 ALARM LIMIT
Defines the alarm limit for motor temperature measurement.
• At motor temperatures above this limit, the drive displays an alarm (2010,
For thermistors:
0 = de-activated
1 = activated
3504 FAULT LIMIT
Defines the fault limit for motor temperature measurement.
• At motor temperatures above this limit, the drive displays a fault (9,
For thermistors:
0 = de-activated
1 = activated
Group 35: Motor Temp Meas
Range
1...8
-10...200 ° C /
0...5000 Ohm /
0...1
-10...200 ° C /
0...5000 Ohm /
0...1
Resolution
Default
1
1
110 ° C /
1
1500 Ohm /
0
MOTOR OVERTEMP
130 ° C /
1
4000 Ohm /
0
) and stops the drive.
MOTOR OVERTEMP
106
S
)
Start-Up

Advertisement

Table of Contents
loading

Table of Contents